Can You Run a Ham Radio Station on a UPS?

Yes, for short outages, but only with a UPS of at least 1000 VA / 600 W behind a 100 W HF rig, and it will not last long. A 21 A key-down through a 13.8 V supply pulls 367 to 494 W and about 640 VA from the wall, more than any 600 VA unit can deliver. For hours of operation, feed the radio straight from a 12 V battery through a DC switch: on receive the same batteries last several times longer.

On this page
  1. What the radios draw
  2. What the wall sees: the power supply decides
  3. How long a UPS runs the station
  4. The DC path: why the battery should feed the radio
  5. Setting up both paths together
  6. Where this answer stops applying
  7. Frequently asked questions

A ham radio is a 13.8 V DC device, and that one fact decides how to back it up. Put a UPS in front of the station and the battery's energy goes through two conversions before it reaches the radio: the UPS turns 24 V DC into 120 V AC, then the power supply turns it back into 13.8 V DC. It works, and for riding through a short outage or finishing a contact it is fine. For keeping a station on the air through a long one, the radio belongs on a battery directly, and the UPS belongs on the computer and network gear around it.

What the radios draw

Every transceiver maker publishes current drain at 13.8 V, and the transmit figure is the one that sizes everything else. These are the published figures.

Published supply range and current drain at 13.8 V DC
RadioSupply rangeReceiveTransmit
Icom IC-7300 (HF/50 MHz, 100 W)13.8 V ±15%0.9 A standby, 1.25 A max audio21 A at 100 W
Yaesu FTDX10 (HF/50 MHz, 100 W)13.8 V ±15%2.5 A no signal, 3.0 A signal23 A at 100 W
Yaesu FT-991A (HF to UHF)13.8 V ±10%1.8 A no signal, 2.2 A signal23.0 A at 100 W HF/50 MHz, 15.0 A at 50 W VHF/UHF
Icom IC-9700 (VHF/UHF/1.2 GHz)13.8 V ±15%1.2 A standby, under 1.8 A max audiounder 18 A, high power
Icom IC-2730A (VHF/UHF mobile, 50 W)13.8 V ±15%1.2 A standby, 1.8 A max audio13 A

The gap between the two columns is the whole story. A 100 W HF rig on receive is a 12 to 41 W load at 13.8 V; on key-down it is a 290 to 317 W load. A UPS has to be sized for the second number and its battery drained by a mix of both.

What the wall sees: the power supply decides

A UPS does not see the radio. It sees the 13.8 V power supply, and that supply's losses and power factor land on the UPS. The best published measurements we found are bench load tests by Eric Lemmon (WB6FLY), hosted on Repeater Builder, whose sheets list AC input watts, VA and power factor at each amp of load from zero up to the supply's limit. Two of them cover the common supply types: an Astron RS-35M linear supply (24 A continuous on the test sheet) and an Astron SS-25 switching supply (20 A continuous, 25 A intermittent).

Measured AC input at about 120 V for the radios' published current, from WB6FLY's load tests
DC loadMatchesRS-35M linearSS-25 switcher
0 ASupply on, radio off16 W, 52 VA8 W, 17 VA
1 ANear IC-7300 receive40 W, 74 VA27 W, 52 VA
3 AFTDX10 receive87 W, 139 VA58 W, 107 VA
13 AIC-2730A transmit316 W, 429 VA223 W, 401 VA
18 AIC-9700 transmit428 W, 560 VA313 W, 555 VA
21 AIC-7300 transmit494 W, 635 VA367 W, 643 VA
23 AFTDX10 / FT-991A transmit537 W, 685 VA404 W, 702 VA

Two things stand out. The linear supply is inefficient: 34% at 1 A, 58% at 21 A, never above 60% in the test. The switcher reaches 78% at 21 A. But the switcher's power factor stayed between 0.52 and 0.60 under load, against 0.78 for the linear at 21 A, so on transmit its VA is no lower. The 21 A and 23 A rows are also past the SS-25's 20 A continuous rating; it held them on the bench but you would not run one there for long. Samlex's spec sheet for its SEC-1235M switcher tells the same story from the other side: 30 A continuous output, a rated input current of 7.5 A at 120 V (900 VA at full load), and a peak efficiency of 85% ±5%.

Our analysis: a 100 W rig is a 650 VA load

Whichever supply you use, a 100 W HF transceiver on key-down puts roughly 640 to 700 VA on the UPS, and 370 to 540 W. That is why the first transmission on battery so often trips the UPS. A typical 600 VA unit is rated about 360 W, and both the linear and switching figures exceed it on both counts. Size on whichever limit you hit first, VA or watts; VA vs watts explains why both exist, and the overload alarm guide covers what happens when you cross one.

So the minimum for a 100 W radio alone is the 1000 VA / 600 W class, where an FTDX10 on a linear supply at 537 W is already 90% of the watt rating. Add a station PC, monitor and network switch and you are in 1500 VA territory. UPS load percentage explains why running near the limit costs runtime and battery life.

How long a UPS runs the station

These estimates use the model behind our UPS runtime calculator: new sealed lead-acid batteries, a Peukert exponent of 1.25 referenced to the 20-hour rating, 88% inverter efficiency and 8 W of inverter overhead. Loads are the measured AC input figures above, interpolated where the radio's current falls between test steps (46 W for the IC-7300's 1.25 A through the linear supply, 31 W through the switcher). Why UPS runtime is not linear covers the method.

Estimated runtime by UPS class, radio and its 13.8 V supply only
Operating patternAC load600 VA (1 x 12 V 7 Ah)1000 VA (2 x 12 V 7 Ah)1500 VA (2 x 12 V 9 Ah)2200 VA (2 x 12 V 18 Ah)
IC-7300 receive, linear supply46 W42 min1 h 40 min2 h 17 min5 h 25 min
IC-7300 receive, switcher31 W1 h 3 min2 h 30 min3 h 25 min8 h 9 min
FTDX10 receive, linear supply87 W21 min49 min1 h 8 min2 h 41 min
IC-7300, 25% of the time on key-down, linear158 W10 min25 min34 min1 h 20 min
IC-7300 on FT8 at 100 W, linear270 WOver rating on TX13 min18 min42 min
IC-7300 continuous key-down, switcher367 WOver rating9 min12 min29 min
FTDX10 continuous key-down, linear537 WOver rating6 min8 min18 min

The mixed rows are averages, our assumption rather than a measurement. The 25% row treats a quarter of the hour as full key-down current, which overstates a voice contact, since SSB does not hold full current between syllables. The FT8 row follows from the WSJT-X guide's 15-second transmit and receive sequences: alternate them at 100 W and you are on the air about half the time. Here is the arithmetic for that row on the 1500 VA unit:

Average load = (46 W + 494 W) / 2 = 270 W; battery draw = (270 W + 8 W) / 0.88 = 316 W, or 13.2 A at 24 V
Runtime = 20 h x (9 Ah / (13.2 A x 20 h))^1.25 = about 0.30 h, or 18 min

Even a 600 VA unit gets 42 minutes from a listening IC-7300, and it can carry a 50 W mobile such as the IC-2730A on transmit (316 W and 429 VA through the linear supply). It cannot carry a 100 W HF key-down. These are new-battery, room-temperature figures; a three-year-old battery delivers less.

The DC path: why the battery should feed the radio

The alternative is a battery wired to the radio's 13.8 V bus through a DC switch. West Mountain Radio's Super PWRgate PG40S is the common example: two 80 A Schottky diodes form an OR gate between the power supply and the battery, so the radio runs from the supply normally and from the battery the instant the supply output fails. It is rated 40 A continuous, has a built-in charger switchable to 1, 4, 7 or 10 A, charges to 13.8 V for gel and 14.2 V for AGM, and floats at 13.5 V.

Two power paths for an IC-7300 on receive. Through a UPS and a linear 13.8 V supply the battery delivers about 61 W to get 17 W to the radio. Through a DC switch the battery delivers about 16 W.
An IC-7300 listening at 1.25 A needs about 17 W at 13.8 V. Through a UPS and an RS-35M linear supply, the battery must deliver about 61 W (46 W at the UPS output, plus inverter loss and overhead). Wired through a DC switch, it delivers about 16 W, roughly a quarter as much.

The difference in runtime follows directly. Take the same two 12 V 9 Ah batteries from a 1500 VA tower and wire them in parallel as 12 V 18 Ah: by the same Peukert model, the IC-7300's 1.25 A receive current takes about 13 hours to exhaust them, against 2 h 17 min through the UPS and linear supply. On transmit the gap narrows but stays: the DC path takes the radio's 21 A from a 12 V battery, roughly 270 W, while the UPS path takes about 570 W ((494 W + 8 W) / 0.88) from its 24 V battery. The DC path wins on every operating pattern.

The 13 hours is battery capacity, not guaranteed operating time, because the radio stops before the battery does. Its floor is the bottom of its published supply range: 11.73 V for the IC-7300, IC-9700, IC-2730A and FTDX10 (13.8 V minus 15%), but 12.42 V for the FT-991A (minus 10%). The PWRgate's diodes drop 0.25 V at 1 A and 0.37 V at 40 A, so the radio sees less than the battery. West Mountain's own shack guide puts the operating window at "13.8V +/- 10 to 15 percent depending on the manufacturer" and warns: "Never go above 14V it can damage equipment." A radio with a 10% tolerance on a 12 V battery has little room, and it shows up first on transmit, when the current is highest.

Bottom line

Put the radio on a DC battery switch and a battery sized for the hours you want, and put the station computer, router and rotator controller on a 1500 VA pure sine UPS. If you must run the radio from a UPS, use at least a 1000 VA / 600 W unit, a switching supply rather than a linear one, and expect minutes of transmitting, not hours.

Setting up both paths together

  1. Measure the station's AC load. Put a plug-in meter on the power supply and key down into a dummy load at full power. Compare the reading with the table above; how to measure power draw covers what the meter can and cannot tell you.
  2. Choose what goes on the UPS. The logging PC, monitor and network gear are AC loads with their own supplies, the kind of load a UPS is built for; UPS for a home office sizes that part, and UPS for a modem and router covers the internet link. For a remote station on satellite internet, see UPS for Starlink.
  3. Put the radio on the DC switch. Supply into the switch, battery into the switch, radio out of it, with a fuse at the battery. West Mountain's guide uses a 50 A fuse on its station battery and DC-rated breakers only.
  4. Match the charger to the battery. Set the PWRgate's charge current and gel or AGM mode to the battery. Sealed AGM and gel batteries are the usual choice indoors; UPS battery types compares them.
  5. Test it. With the radio receiving, switch off the power supply's breaker and confirm the radio keeps running. Then key up briefly and watch the radio's voltage reading against its floor.

For a small DC-only setup, such as a VHF/UHF mobile used as a base station, a compact DC backup unit may be enough; DC mini UPS vs AC UPS explains the trade, though most mini units are sized for routers, not a 13 A transmitter.

Where this answer stops applying

  • Other supplies. The watts and VA above come from one sample each of two Astron models, tested at about 120 V. Another supply, especially a modern switcher with power factor correction, will differ. Measure yours.
  • Amplifiers. A linear amplifier is a separate AC load on top of the radio, and none of the figures here include it. Measure it before putting it on any UPS.
  • QRP and handhelds. Radios that run from their own internal batteries or draw a few amps on transmit change the math entirely. This page is about 100 W class stations.
  • Long outages. Neither a UPS nor a station battery replaces a generator or solar charging for multi-day events. Using a UPS with a generator covers bridging the gap while one starts.

Turn the supply on before the outage, not during it

Samlex lists the SEC-1235M's inrush current at start-up as 30 A ±5 A for under 5 ms. Switching a big 13.8 V supply on while the UPS is already on battery adds that surge to whatever else the UPS is carrying. Leave the supply running and let the DC switch or the UPS take over when the power fails.

Frequently asked questions

Will a 600 VA UPS run a 100 W HF transceiver?

On receive, yes: an IC-7300 through a linear supply draws about 46 W. On transmit, no. At the IC-7300's 21 A, measured supply input is 367 to 494 W and 635 to 643 VA, above a typical 600 VA unit's 360 W and 600 VA ratings. Expect an overload alarm or shutdown the first time you key up at full power.

Is a switching or linear power supply better on a UPS?

A switcher wastes less, so the battery lasts longer: in WB6FLY's tests, 31 W against 46 W at an IC-7300's receive current, and 367 W against 494 W on transmit. It does not shrink the VA, because the tested SS-25 ran at a power factor of about 0.57 against the RS-35M's 0.78. Size the UPS on VA and watts both.

How long will a car battery run my ham radio?

Divide the battery's amp-hours by the radio's average current, then derate. An IC-7300 listening at 1.25 A would take 14.4 hours to draw 18 Ah by simple division (about 13 once the Peukert effect is counted), but transmitting cuts that sharply because 21 A for every minute on the air adds up fast. The radio also stops at its low-voltage limit, which comes before the battery is flat.

Can I charge my station battery from the UPS during an outage?

You can, but you lose twice: once in the UPS inverter and again in the 13.8 V supply or charger. In WB6FLY's test the RS-35M was 34% efficient at 1 A and never better than 60%, before counting the UPS. If the battery is going to power the radio anyway, connect it to the radio through a DC switch and skip the conversion.

Does a UPS add noise on HF?

None of the documents cited here addresses it, and it depends on the unit. Test your own: tune across the bands you use with the UPS on utility power, then pull its plug and listen again while it runs on battery. If the noise floor rises, move the UPS away from the rig and its feed lines, or keep the radio on the DC path.

Sources and further reading

  1. Icom America: IC-7300 specifications
  2. Icom America: IC-9700 specifications
  3. Icom America: IC-2730A specifications
  4. Yaesu UK: FTDX10 specifications
  5. Yaesu UK: FT-991A specifications
  6. Repeater Builder: Power supply load tests performed by Eric Lemmon WB6FLY (Astron RS-35M, 2 Feb 2011; Astron SS-25, 18 Mar 2011)
  7. Samlex America: SEC-1235M power supply specifications
  8. West Mountain Radio: Super PWRgate PG40S specifications
  9. West Mountain Radio: Battery Back-up for Your Shack
  10. WSJT-X 2.6.1 User Guide (FT8 15-second T/R sequences)