On this page
No, not into the battery outlets. A laser printer fuses toner with a heated roller, and warming that roller up is a heater load: Brother rates its HL-L2350DW at about 1,104 W peak, more than a common 1500 VA desktop UPS can deliver. Every UPS maker and every printer maker whose documents are cited below says the same thing about battery power. Where they part company is the UPS's surge-only outlets, and that split is why the question keeps getting asked.
This page sets the rules from five makers side by side, lists the published power figures, and shows what a UPS would actually do with a laser printer if you tried.
What the UPS makers and printer makers say
| Document | Battery outlets | Surge-only outlets | What it recommends instead |
|---|---|---|---|
| APC FAQ FA158812 (Back-UPS, Back-UPS Pro, SurgeArrest) | No | No | A separate surge protector and the printer's own circuit; if a UPS is unavoidable, a Smart-UPS sized for the printer's maximum draw, typically 1500 VA or larger |
| APC FAQ FA158811 (Back-UPS shutdowns) | "APC NEVER RECOMMENDS BATTERY BACKING UP A LASER PRINTER." | Not addressed | Listed as a cause of overload shutdowns |
| CyberPower CP1350PFCLCD / CP1500PFCLCD manual | "DO NOT plug a laser printer..." | Printers go here; lasers not singled out | Full-time surge outlets for printers and scanners |
| Lexmark user's guides (B2236, MS310) | "Do not use this product with extension cords, multioutlet power strips, multioutlet extenders, or UPS devices." | Wall outlet; only a Lexmark Inline Surge Protector | |
| Xerox KB0048341 (Phaser 6000 to 6022, WorkCentre 6025/6027) | "Disconnect the power cord from the UPS, and then connect it to a different power outlet." | A different power source | |
| Brother Product Safety Guide (HL-L2350DW family) | UPS not named; "DO NOT connect it to a DC power source or inverter." | Wall outlet; "Brother strongly recommends that you DO NOT use any type of extension cord." | |
Lexmark gives the reason in one sentence: "The power capacity of these types of accessories can be easily overloaded by a laser printer and may result in a risk of fire, property damage, or poor printer performance." It goes further than anyone else on surge protection, too: "Only a Lexmark Inline Surge Protector that is properly connected between the printer and the power cord provided with the printer may be used with this product."
The Xerox entry is a troubleshooting step for a family of small color lasers, which says something on its own: the printer's support pages treat a UPS as a possible cause of the fault. The Brother guide does not mention a UPS, but a line-interactive UPS on battery is an inverter, so the battery side is ruled out there as well. UPS types explained covers why.
The surge-only outlet question, settled
Two answers circulate. One says the surge-only outlets are fine, because they never run from the battery. The other says keep the printer off the UPS entirely. Both come from UPS makers.
The first comes from the outlet labels. CyberPower's manual says to plug "the other peripheral equipment (eg. printer, scanner, speakers, etc.) into the full time surge protection outlets," and APC's 1997 Back-UPS Pro manual described its surge outlets as "for equipment that need surge protection but do not need power during a utility outage (like an inkjet printer or scanner)." Neither manual bans a laser printer from those outlets, so readers fill the gap in the obvious direction. Note that APC's example was an inkjet.
The second comes from APC's dedicated laser printer FAQ, which says the printer should not be plugged into the battery outlets "OR" the surge-only outlets. Its reason is the printer's current draw: it can pull the line voltage down, and the UPS answers a sag by going to battery, again and again, until the battery is drained. Plugging the printer into the UPS's own surge outlets puts that current through the same input cord and the same wall receptacle the UPS is measuring.
Bottom line
APC's answer is the one to follow, because it is the only document here written about laser printers specifically, and it is stricter than the outlet labels, not looser. The outlet labels were never a laser printer endorsement. The wall is the placement every document allows. If your UPS manual names a laser printer as acceptable on its surge outlets, that manual governs your unit.
The same sag is why a UPS can click to battery when a laser printer warms up on the same circuit, even with the printer plugged into the wall. UPS keeps switching to battery covers that diagnosis, and brownouts and voltage sags explains the mechanism.
What laser printers draw
Printer makers publish three kinds of figure: an average while printing, a peak, and sometimes a current. They answer different questions.
| Printer | Printing | Peak or maximum | Ready / sleep | Source |
|---|---|---|---|---|
| Brother HL-L2325DW, HL-L2350DW | about 460 W | about 1,104 W | 48 W / 3.9 W | Brother user's guide |
| Brother HL-L2370DW, HL-L2379DW | about 500 W | about 1,104 W | 48 W / 4.4 W | Brother user's guide |
| Lexmark MS310, MS312 | 520 W average (simplex) | 7.6 A while printing (110 to 127 V) | 6.5 to 7 W / 3 W | Lexmark technical reference |
| Lexmark MS510 | 600 W average (simplex) | 7.6 A while printing (110 to 127 V) | 7 W / 2.5 W | Lexmark technical reference |
| Lexmark MS610dn | 640 W average (simplex) | 7.6 A while printing (110 to 127 V) | 9.2 W / 2.6 W | Lexmark technical reference |
| Lexmark MX61x (multifunction) | 640 W printing, 660 W copying | 8.2 A maximum while printing (120 V) | 20 W / 8 W | Lexmark technical reference |
| Canon imageCLASS LBP122dw (220 to 240 V model) | 530 W | 1,300 W maximum | 3.5 W / 1.0 W | Canon Asia specifications |
The printing average sets runtime. The peak and the current set whether the UPS survives the first page at all. Brother's 1,104 W peak is above the output rating of every 1500 VA desktop UPS that delivers 900 or 1,000 W. Lexmark lists 7.6 A while printing in the 110 to 127 V range; at 120 V that is about 910 VA, nearly all of a 1000 VA unit's rating before anything else is plugged in. That fits APC's "1500va or larger" floor. VA vs watts explains why the current figure and the watt figure give different answers.
The average also hides how the draw arrives. Duplex printing is lower on Lexmark's table (340 to 460 W), and Brother's Quiet Mode drops printing to about 255 W. Neither helps a UPS much: Brother lists a single peak figure for these models, and the peak is what overloads it. For your own printer, the rating label and a plug-in meter on the first page after a cold start give the real numbers; see how to measure power draw.
What a UPS would actually give you
These estimates use the model behind our UPS runtime calculator: new sealed lead-acid batteries, a Peukert exponent of 1.25 referenced to the 20-hour rating, 88% inverter efficiency and 8 W of inverter overhead. They assume the UPS survives the warm-up peak, which on desktop units it mostly will not.
| UPS class (battery) | 48 W (Brother, ready) | 460 W (Brother, printing) | 600 W (Lexmark MS510) |
|---|---|---|---|
| 600 VA / 360 W (1 x 12 V 7 Ah) | 40 min | over rating | over rating |
| 1000 VA / 600 W (2 x 12 V 7 Ah) | 1 h 35 min | 7 min, peak over rating | at the limit |
| 1500 VA / 900 W (2 x 12 V 9 Ah) | 2 h 11 min | 9 min, peak over rating | 7 min, peak unknown |
The worked example for the Brother printing figure on a 1500 VA tower:
Nine minutes of printing, after the UPS has survived a peak above its rating. The ready-state column looks generous, but a printer idling on battery is doing nothing useful, and the first job sent to it triggers the warm-up the UPS cannot carry. Our guide to why runtime is not linear covers each term in the formula.
Our analysis: there is nothing to save
A UPS earns its place by protecting something an outage would destroy: unsaved work, a disk mid-write, a network connection. A print job has none of that. The document stays on the computer, and when the power returns you print it again, losing at most the sheet that was in the fuser. Battery-backing the printer spends the most expensive watts in the house on the one load that loses nothing. Spend the capacity on the computer, monitor and router instead; the home office guide sizes that setup.
Where to plug it instead
- Plug the printer into a wall receptacle, not the UPS, and not an extension cord. Brother strongly recommends against any extension cord, and Lexmark rules out cords and power strips; see plugging a UPS into a power strip for the same rule from the UPS side.
- Give it a different circuit from the UPS if you can. APC recommends the printer have its own circuit, and CyberPower's manual says the UPS's wall outlet should not serve equipment with large electrical demands, naming copiers.
- Add surge protection the printer maker allows. For a Lexmark, that is only a Lexmark inline surge protector. For others, APC says a separate surge protector is adequate; surge protector ratings explains what to look for on the box.
- Move it if the UPS is already complaining. An overload beep the moment a job starts is the classic sign; UPS overload alarm walks through clearing it.
Where this answer stops applying
- Large online UPS systems. APC's FAQ leaves room for a Smart-UPS sized to the printer's maximum draw, and office copiers and production printers on large online systems are a facility design question for the printer's service provider, not a desktop UPS one.
- Inkjets, thermal label printers and receipt printers. None of them has a fuser, and none of the bans here covers them. The small business POS guide covers receipt printers at the counter.
- Your own manuals. The quotes here come from specific models. Search your printer's safety section for "UPS," "inverter" and "extension cord," and your UPS manual for "laser"; a UPS warranty can also hinge on it, as UPS warranties and equipment guarantees explains.
Frequently asked questions
Can I plug a laser printer into the surge-only outlets on my UPS?
It depends on whose advice you follow, and APC's is the stricter. CyberPower's CP1500PFCLCD manual sends printers to the full-time surge outlets and only bans laser printers from the battery side. APC's laser printer FAQ says not to use the battery outlets or the surge-only outlets, because the printer's current draw can push the UPS onto battery. The wall is the answer both allow.
Why does my UPS click or beep when the laser printer starts?
The printer is pulling the voltage down. A small Brother laser is rated at about 1,104 W peak, and on a shared circuit that sag can drop the input below the UPS's transfer threshold even when the printer is plugged into the wall nearby. APC recommends giving the printer its own circuit for this reason.
Will a laser printer damage a UPS?
The makers' stated concern is overload rather than a specific damage mechanism. Lexmark says these accessories can be easily overloaded by a laser printer, with a risk of fire, property damage, or poor printer performance. CyberPower's manual says exceeding the rated capacity may cause the UPS to shut down or its circuit breaker to trip.
Is an inkjet printer OK on a UPS?
Inkjets have no fuser, the part that makes a laser a heater load, and none of the UPS documents cited here ban them. The 1997 APC Back-UPS Pro manual and CyberPower's current manual both list printers as surge-outlet equipment, since nothing printing needs to keep running in an outage.
What surge protector should I use for a laser printer?
Follow the printer maker first. Lexmark allows only a Lexmark Inline Surge Protector connected between the printer and its own cord. APC says a separate surge protector is adequate for most laser printers. Brother strongly recommends no extension cord of any type. Protection at the panel avoids the question; see whole-house surge protection.
Sources and further reading
- APC by Schneider Electric FAQ FA158812: Recommendations for protecting a laser printer
- APC by Schneider Electric FAQ FA158811: Back-UPS equipment shuts down or reboots
- CyberPower: CP1350PFCLCD / CP1500PFCLCD user manual
- APC: Back-UPS Pro 280/420/650 user's manual, 990-2037B (1997)
- Lexmark B2236 user's guide: Product statements (power cord, UPS and surge protector)
- Lexmark MS310 to MS610 and MX310 to MX61x technical reference: Power requirements
- Xerox support KB0048341: Make sure the printer is not connected to an uninterruptible power supply (UPS)
- Brother: Product Safety Guide, HL-L2325DW / HL-L2350DW / HL-L2370DW and related models
- Brother online user's guide: General specifications, HL-L2325DW / HL-L2350DW / HL-L2370DW
- Canon: imageCLASS LBP122dw specifications