Yes, a UPS can carry an outdoor wood boiler through a short outage, but it is not keeping the fire going. It is keeping the water moving. An outdoor furnace is a large tank of water wrapped around a firebox, and when the power fails, the fan that feeds the fire stops along with the pump that carries the heat to the house. The fire dies down; the heat already in the firebox does not leave with it.
What an outage actually threatens
Most people who search this are trying to keep the house warm. The manuals worry about something else: the furnace itself, with a load of burning wood and no circulation. Two of them put it in writing.
- Portage & Main (ML30, ML36, ML42): "We recommend a hot water circulation loop that will dissipate at least 10% (ten percent) of the estimated heat output of the water furnace in the event that circulation is reduced because of electrical power failure." The loop must be one that "can only be made inoperative by a deliberate manual action", in pipe of at least 0.75 inch. The Ultimizer BL 2840 and BL 3444 manual repeats it word for word.
- WoodMaster CleanFire 400: among the conditions it lists for boilers connected to an existing system is that they "have provision for preventing, or adequate water capacity within the boiler to prevent, damage to the boiler from loss of circulation due to electrical power failure."
The cost of getting it wrong is spelled out too. WoodMaster's troubleshooting section says: "If the water in the outdoor furnace boils, air can enter the lines and could damage the pump." Central Boiler tells owners that if the water "ever boils, be sure to check the water level and restore to full", and that any added water must be dosed with corrosion inhibitor to the proper level again.
What the fire does when the power fails depends on the design. On a Portage & Main the control "will turn the combustion fan off to close the air damper", so a dead fan means a closed damper. WoodMaster says of its gasifying CleanFire that "the air flow to the fire will be stopped and the fire will go out", and that it must be relit when power returns. Neither maker wants more fuel in it: "Do not load the Outdoor Water Furnace with wood during an electrical power failure" (Portage & Main) and "Do not attempt to fire the CleanFire during a power outage" (WoodMaster).
Our analysis: back up the pump first, the furnace second
The pump is the load that protects the furnace and delivers the heat. The furnace's own controls and fan are the load that keeps it burning, and the manuals do not ask for that during an outage. A pump-only backup is smaller, runs longer, and does what the manuals care about. Backing up the whole furnace is reasonable too, but it is a bigger job and buys less time.
What the pump and the furnace draw
Outdoor boilers push water through long underground runs, so they often use bigger circulators than an indoor boiler. Here are the published figures, all at 115 or 120 V.
| Equipment | Type | Published rating | Source |
|---|---|---|---|
| Taco 007e | ECM circulator | 44 W max, 0.54 A | Taco submittal 101-177 |
| Grundfos UPS15-58FC | 3-speed PSC circulator | 60 / 80 / 87 W | Grundfos spec sheet |
| Grundfos UPS26-99FC | 3-speed PSC circulator, 1/6 hp | 150 / 179 / 197 W (1.3 / 1.5 / 1.8 A) | Grundfos submittal |
| Taco 0011 | PSC circulator, 1/8 hp | 1.76 A (watts not stated) | Taco submittal 101-034 |
| WoodMaster 3300 | Whole furnace | 0.5 A idle, 1.5 A average, 6 A max | WoodMaster manual |
| WoodMaster 4400 | Whole furnace | 0.5 A idle, 2.5 A average, 6.9 A max | WoodMaster manual |
| WoodMaster 5500 | Whole furnace | 0.5 A idle, 3.5 A average, 7.5 A max | WoodMaster manual |
| WoodMaster CleanFire 400 | Whole boiler | 10 A rating, 15 A circuit | CleanFire manual |
Read the WoodMaster numbers carefully. The manual notes that its amp draw "may vary depending on the revision of your furnace and external devices attached", and that the maximum "can only occur when all devices are operating; this only happens momentarily at the start-up." Amps times volts is VA, not watts (see VA vs watts), so 2.5 A at 120 V is a 300 VA average, and the real watts are 300 or less. The 6.9 A start-up peak is about 830 VA for a moment, which a 1500 VA UPS covers. A UPS run close to its limit, though, can trip its overload alarm when everything starts at once.
The Taco 0011 has the same catch: 1.76 A at 115 V is about 202 VA, a ceiling for sizing, not a running figure. If your pump label shows only amps, a plug-in meter on the real pump beats both numbers; how to measure power draw covers the method.
How long a UPS runs it
The figures below use the method from why UPS runtime is not linear: 85% inverter efficiency and a Peukert exponent of 1.15 for AGM batteries, on a common 1500 VA tower with two 12 V 9 Ah batteries (216 Wh nominal).
| Load | Watts | Battery current | Runtime |
|---|---|---|---|
| Taco 007e at maximum | 44 W | 2.2 A | about 3 h 15 min |
| Grundfos UPS15-58FC on speed 3 | 87 W | 4.3 A | about 90 min |
| Grundfos UPS26-99FC on speed 1 | 150 W | 7.4 A | about 48 min |
| Grundfos UPS26-99FC on speed 3 | 197 W | 9.7 A | about 35 min |
| Whole WoodMaster 4400 at its average (300 VA ceiling) | 300 W or less | 14.7 A or less | at least 22 min |
The arithmetic for the UPS26-99 on high: the battery supplies 197 W / 0.85 = 232 W, which is 9.7 A at 24 V.
Here is where an outdoor boiler differs from the indoor gas boiler, whose zone pumps start and stop with the thermostats so the UPS lasts longer than the continuous figure. WoodMaster says its pump "cannot be wired to thermostats that only run the pump when the building calls for it", and Central Boiler says "at least one circulation pump must run continuously." On these furnaces the continuous figure is the runtime. Treat it as a new-battery number, and run your own load through the runtime calculator.
The speed setting is worth checking. The UPS26-99's speed 1 draws 47 W less than speed 3 and adds about 13 minutes on the same UPS. If the system heats the house acceptably on a lower speed, setting it there before winter costs nothing.
For hours instead of minutes
For several hours of circulation, use an inverter/charger on a deep-cycle battery, the same setup the pellet stove guide works through, or a UPS that takes extended battery packs. As a rule of thumb, using half of a 12 V 100 Ah battery (600 Wh) at 85% efficiency gives roughly 11 hours at 44 W, 6 hours at 87 W and 2.5 hours at 197 W.
The wiring problem: the pump is fed through the furnace
This is the part most forum advice skips. On the two designs here that document their pump wiring, the circulator does not plug into a wall in the house.
- WoodMaster 3300, 4400, 5500: the pump is wired into the furnace's junction box. "The wires from the pump will have to connect with the main power wires in the junction box along with the power wires from the ETC System." The furnace is fed by "a 14-2 (two wires plus ground) underground rated wire", and the manual recommends that "the incoming fuse or circuit breaker not exceed 15 amps."
- Central Boiler Classic Edge: the pump kits list a Grundfos UPMS 20-58 F with a 32-inch power supply cord, and the wiring diagram shows a pump-compartment receptacle marked "10 Amp Max" behind the furnace's 5 A circuit breaker. "A certified electrician must do the electrical installation," the manual says.
So power for both furnace and pump comes from a hardwired circuit in the house panel, buried in the trench. A UPS cannot simply be plugged in anywhere along that path.
| Goal | Approach | Who does it |
|---|---|---|
| Keep the whole furnace powered | UPS at the house end, feeding the furnace circuit through a power inlet and manual transfer switch | Electrician, to local code |
| Keep only the pump running | Pump on its own circuit or receptacle that the UPS can feed, with the furnace on utility power | Electrician, to the furnace maker's instructions |
| Hours of backup, or a long outage | Generator on an approved transfer switch, with the UPS bridging the start-up gap if wanted | Electrician, to local code |
| Protection that needs no power | Portage & Main's heat-dissipation loop, sized to at least 10% of output | Heating installer |
Keep the UPS indoors at the house end, not in the furnace's pump compartment, where heat and weather are hard on batteries and electronics; see where to place a UPS. Hardwired vs plug-in UPS explains the inlet and transfer switch options, and using a UPS with a generator covers the bridge setup. Never backfeed a circuit through a male-to-male cord.
Waveform: none of these manuals states a waveform requirement. Our recommendation is a pure sine wave UPS anyway. ECM circulators such as the 007e are electronic drives, and a whole-furnace backup also runs the furnace's control electronics; the Classic Edge's wiring diagram shows a 24 VDC and 5 VDC power supply behind its control panel.
How big a heat-dump loop is
Portage & Main's 10% rule is the power-free alternative, and it is bigger than it sounds. As an illustration with a rating from another maker, Central Boiler lists the Classic Edge 560 at 200,000 Btu/hr. Ten percent of that is 20,000 Btu/hr, about 5.9 kW of heat, roughly what four 1,500 W space heaters give off. A loop that sheds that much without a pump is a heating installer's design, not a UPS question, but it explains why a pump on battery is the common choice.
Bottom line
Size the backup on the circulator: 44 W for an ECM pump, up to 197 W for a UPS26-99 on high. A 1500 VA pure sine UPS runs those for about 3 hours down to 35 minutes, continuously, since the pump must not cycle. Because the pump is fed through a hardwired furnace circuit, have an electrician put the UPS at the house end with an inlet and transfer switch. For long outages, plan glycol or a generator.
Where this answer stops applying
- Long outages in hard cold. Central Boiler's answer for a prolonged power failure is a generator "to prevent lines from freezing", and for lengthy outages in cold weather, propylene glycol at no less than 30% concentration. WoodMaster's manual says the same about glycol. A UPS covers the start of an outage, not a three-day ice storm.
- Indoor wood boilers. The heat stays in the building and the piping is different. The pump logic carries over; the trench and outdoor wiring do not.
- Your own furnace. The figures above are from these models and pumps. Other makers and revisions differ, and WoodMaster warns that amp draw varies by revision. Check the nameplate, or measure.
- Unattended furnaces. Central Boiler says the furnace "is not intended to be the only source of heat", and wants an alternate heat source in place if it is left unattended or runs out of fuel. A UPS does not change that.
Test it before the first storm
With a normal fire going, switch off the breaker feeding the UPS and confirm the pump keeps running and the house heat exchanger stays warm. Time it against the table above. When power returns, check the furnace water level, and relight if your model requires it.
Frequently asked questions
What happens to an outdoor wood boiler when the power goes out?
The combustion fan stops. On a Portage & Main the control closes the air damper by turning that fan off, and WoodMaster says the CleanFire's "air flow to the fire will be stopped and the fire will go out". The wood already burning keeps heating the water jacket, but the circulator has stopped too, so the heat has nowhere to go except into the jacket water.
Should I load wood into my outdoor furnace during a power outage?
No, according to the two makers who address it. The Portage & Main manual says "Do not load the Outdoor Water Furnace with wood during an electrical power failure", and WoodMaster says "Do not attempt to fire the CleanFire during a power outage." A UPS that keeps the pump running is for moving the heat already in the furnace, not for running a full burn.
Will a UPS keep my outdoor boiler lines from freezing?
For a few hours at most. Central Boiler's own answer for long outages is a generator "to prevent lines from freezing", or a nontoxic propylene glycol mix of at least 30% if lengthy outages are anticipated in cold weather. WoodMaster's manual gives the same antifreeze advice. A UPS covers the first part of an outage; glycol or a generator covers a long one.
Can I use a battery and inverter instead of a UPS?
Yes, and for more than an hour it is the better tool. An inverter/charger on a 12 V deep-cycle battery switches over like a UPS but carries far more energy. By our arithmetic, using half of a 12 V 100 Ah battery at 85% inverter efficiency gives roughly 6 hours at 87 W and 2.5 hours at 197 W. The pellet stove guide covers the same setup.
Is a UPS26-99 too big for a UPS?
Not for the watts: 197 W on speed 3 is well inside a 1500 VA unit's rating. The problem is energy. The same pump on speed 1 draws 150 W per its Grundfos data sheet, which adds about 13 minutes on a 1500 VA tower. If the system still heats the house on a lower speed, setting it there before winter is the cheapest runtime you can buy.
Sources and further reading
- Central Boiler: Classic Edge Titanium HDX Owner's Manual (p/n 9001193, Rev. A)
- WoodMaster: Owner's Manual, Outdoor Wood Furnace 3300, 4400 Heavy Duty, 5500 Heavy Duty
- WoodMaster: CleanFire 400 Owner's Manual (Rev 2.1.4)
- Portage & Main: Installation and Operation Manual, Models ML30, ML36 and ML42
- Grundfos: UPS26-99FC (52722512) Submittal Data
- Grundfos: UPS 15-58 FC (59896341) Specification Sheet
- Taco: 007e ECM High-Efficiency Circulator Submittal Data 101-177 (effective August 16, 2021)
- Taco: 0011 Cartridge Circulator Submittal Data 101-034 (effective January 12, 2015)