No. A power vent water heater will not heat water in a power outage, even with the gas on. It needs 120 V for two jobs: lighting the burner and pushing the exhaust outside. Without both, the gas valve stays shut. A UPS can bring both back, but only if the heater plugs in with a cord.
First, the terms. A power vent water heater is a gas tank heater with an electric fan, called a blower, on top. The blower pushes the exhaust out through a plastic pipe, often sideways through a wall. An older atmospheric vent heater has no fan. Its hot exhaust rises up a metal flue to a chimney on its own. A hot surface igniter (HSI) is a small part that glows red hot and lights the gas. It replaces the always-lit pilot flame of older tanks. A UPS (uninterruptible power supply) is a battery box that keeps its outlets live when the wall power fails.
Why it stops: what runs on 120 V
A.O. Smith's manual shows the order of events each time the heater fires. The control checks the blower's air pressure switch. Then the blower starts, and the switch must prove it is moving air. Only then is the igniter powered and the gas valve opened. The control must sense flame, or it shuts the gas off. When the water is hot, the burner stops and the blower runs on for a short post-purge to clear the pipe.
The service handbook gives the times. Pre-purge runs 5 seconds on natural gas and 15 on propane. The igniter warms for 10 seconds. Post-purge runs 30 seconds. So the blower runs the whole burn plus about 45 seconds. With no power, none of this starts. The manual's own troubleshooting chart lists the first cause of "blower will not start" as "No power to unit."
This is the point many guides blur. "Gas water heaters work in an outage" is true of one kind of tank, not all of them. A standing-pilot tank with an atmospheric vent keeps heating. A power vent tank does not.
What the makers say it draws
| Heater or part | Electrical rating | Ignition | Recovery at 90°F rise | Source |
|---|---|---|---|---|
| A.O. Smith ProLine XE GPVL-50 (40,000 BTU/h, 49 gal rated) | 120 V, 5 A | Electronic hot surface igniter | 44.7 gal/h | A.O. Smith product page |
| Rheem residential 40 and 50 gal power vents | Maximum current draw "approximately 5.0 amps" | Hot surface ignitor | Not stated | Rheem AP22548 |
| Rheem residential 75 gal power vent | Maximum current draw "approximately 5.0 amps" | Hot surface ignitor | Not stated | Rheem AP22670 |
| Rheem Performance XG50S06PV36UO (36,000 BTU/h, 48 gal rated) | Standard 120 VAC connection | Silicon nitride ignitor (HSI) | 36.4 gal/h | Rheem spec sheet |
| Replacement exhaust blower motor for A.O. Smith heaters (183381-000) | 1.8 A at 115 V, 1/20 hp | n/a | n/a | Parts listing |
Five amps at 120 V is 600 VA. That is a ceiling, not a running figure. Rheem's own words are "maximum current draw." A replacement exhaust blower motor sold for A.O. Smith heaters is rated 1.8 A, about 207 VA at 115 V. It may not be the motor in your model. But it shows how far below 5 A the blower, the part that runs all through the burn, can sit. Neither maker publishes watts while running or at idle. So the only way to know your heater's draw is to measure it. A plug-in meter works on a corded heater, and how to measure power draw shows the method. Read the meter during a burn, and again while the heater sits idle.
What size UPS a power vent heater needs
Size for the worst case first. If you have not measured, treat the heater as 600 W at its peak. A UPS's watt rating, not its VA figure, is what limits the load (VA vs watts explains why). A 1000 VA unit is often rated about 600 W, which would leave no headroom at all. A 1500 VA unit rated 900 to 1000 W carries 600 W at 60 to 67% of its rating. That is the class to buy.
Once you have a measured figure, you may find a smaller unit would carry it. But the watt rating is the easy part. Battery energy decides how long the heater runs, and bigger units carry more of it.
Waveform
Buy a pure sine wave UPS. Neither A.O. Smith nor Rheem states a waveform rule, so this is our recommendation, not theirs. It rests on two things in the manuals. First, the blower is an AC motor, and motors run hotter on the stepped output of a "simulated sine" UPS. Second, the flame is proven by a tiny current. A.O. Smith's handbook times its flame failure response "@ 1uA flame current", one millionth of an amp. The gas furnace guide explains how a stepped wave can make a good flame read as no flame. When that happens, the heater tries three times and then locks out. A.O. Smith's handbook lists that soft lockout as 20 minutes.
Worked case: a GPVL-50 on a 1500 VA UPS
Take an A.O. Smith GPVL-50 plugged into a 1500 VA pure sine UPS with two 12 V 9 Ah batteries. Suppose your meter reads 150 W while the blower runs. That figure is picked for this walkthrough. It is not published, so use your own reading.
The estimate uses the model behind our UPS runtime calculator: new sealed lead-acid batteries, 88% inverter efficiency and 8 W used by the UPS itself. It also allows for lead-acid giving up less of its charge when drained fast. UPS runtime explained covers each term.
Runtime = 20 h x (9 Ah / (7.5 A x 20 h))^1.25 = about 0.6 h, or 36 minutes of blower time
Now turn minutes into hot water. The GPVL-50 recovers 44.7 gallons per hour at a 90°F rise. Say a family draws 20 gallons of hot water, and 20 gallons of cold water flow in to replace it. Reheating them works out like this:
Blower time = 27 minutes + about 45 seconds of purges = about 28 minutes
So that battery gives about one 20 gallon reheat, with a little to spare. A full tank of cold water, 49 gallons, needs about 66 minutes of burner time. That is more than this UPS holds. The time between burns also costs something. The UPS uses its own 8 W the whole time, plus whatever the heater draws at idle.
| Measured draw | 1000 VA (2 x 12 V 7 Ah) | 1500 VA (2 x 12 V 9 Ah) | 2200 VA (2 x 12 V 18 Ah) |
|---|---|---|---|
| 100 W | 42 min | 58 min | 2 h 17 min |
| 150 W | 26 min | 36 min | 85 min |
| 200 W | 19 min | 25 min | 60 min |
| 300 W | 11 min | 16 min | 37 min |
| 600 W (nameplate maximum) | 5 min, at full load | 7 min | 16 min |
Divide your row by 28 minutes to count 20 gallon reheats on a GPVL-50. At 150 W, a 2200 VA tower gives about three.
Our analysis: the tank is already a battery
The burner stops in an outage, but the water already heated does not vanish. It sits in an insulated tank of about 49 gallons, and city water pressure still pushes it out. So the first hours of an outage often need no UPS at all. The UPS earns its place in a long outage, when that stored heat is gone. Hold its battery for one planned reheat, not for keeping the tank topped up all day.
The cord is what makes a UPS possible
A plug-in UPS needs a plug. A.O. Smith ships the heater with a 6 foot power cord and says a grounded outlet "must be within reach" of it. But it adds that the cord "may be used on a unit only where local codes permit." Where code does not, the installer cuts the cord and wires the heater in. Rheem's manuals say the same: use the cord "if local codes permit," or else connect a 120 V supply to the leads in the control box.
So look at your heater first. If it has a cord in a wall outlet, a UPS is a plug-in job. If it is wired in, a desktop UPS cannot feed it. The choices then are an inlet with a transfer switch or a hardwired UPS, and both are electrician work. Hardwired vs plug-in UPS covers them.
What the manuals allow
Neither maker's manual mentions power outages, UPS units or generators. They do set rules that any backup source has to meet:
- No extension cord. A.O. Smith: "Do not use an extension cord." Rheem: "DO NOT use an extension cord." Put the UPS within reach of the heater's own cord.
- Grounded. Both require a grounded supply. Plug the UPS into a grounded outlet, and never use an adapter that drops the ground pin.
- Polarity. A.O. Smith calls the heater "polarity sensitive." It "will not operate properly" if the supply's hot and neutral are reversed.
- No GFCI. A.O. Smith says "Do not use a GFI outlet." Rheem says a GFCI circuit is "not recommended."
Those rules matter most on a generator. In our view, a generator whose neutral is not bonded to ground can cause the same flame-sense faults a furnace shows. So feed the heater through a transfer switch set up by an electrician, as using a UPS with a generator describes.
Setting it up
- Read the nameplate and check for a cord. No cord means the plug-in route is closed.
- Measure. Note the watts during a burn and at idle.
- Plug the heater into a battery outlet. Most UPS units also have surge-only outlets that go dead in an outage.
- Check for a light-load cutoff. APC says Back-UPS models with No-load Shutdown turn off on battery when the load is under 15 W, after about 15 minutes. Between burns, the heater idles. If your idle reading is under 15 W, the UPS may shut off before the next call for heat. APC's FAQ shows how to turn the feature off. See UPS shuts off during an outage.
- Test it. Run some hot water, then switch off the breaker feeding the UPS. Watch the heater light and burn on battery. If it tries three times and stops, suspect the waveform.
Which gas tank heaters need power
| Heater type | Heats in an outage? | Backup that works |
|---|---|---|
| Atmospheric vent, standing pilot, millivolt gas control | Yes. The pilot powers the control | None needed |
| Power vent with a cord | No. Blower and igniter need 120 V | 1500 VA pure sine UPS, or a generator through a transfer switch |
| Power vent, hardwired | No | Electrician-installed inlet and transfer switch, or a hardwired UPS |
| Gas tankless | No | See the tankless guide |
The standing-pilot tank works because its pilot flame makes its own power. Bradford White describes its ICON control this way: a thermopile "converts heat energy from the pilot flame into electrical energy" to run the gas valve and electronics. Its words: "No external electricity required." A quick check on your own tank: if it has no cord and no wires running to it, it does not need the grid. A gas tankless heater has the same problem as a power vent, with a smaller load. The tankless guide covers it. Hot water heat from a gas boiler is sized by its circulators instead.
Where this answer stops applying
The runtimes are model estimates for new batteries, worked from a draw picked for the example. Your meter reading and a timed test on battery are the only true numbers. The figures here come from A.O. Smith and Rheem documents. Other makers and older models may differ, so read your own manual. This page is about tank heaters. Power direct vent models, condensing tanks and electric tanks are outside it. A UPS keeps the blower running only while the battery lasts. If the battery dies mid-burn, the heater stops just as it does in any outage. Homes on a well lose water pressure in an outage too, and a well pump needs far more than a UPS. For outages that last days, a generator on a transfer switch fits better. UPS vs generator walks through that choice. Keep carbon monoxide alarms working whatever you use.
Frequently asked questions
Will a power vent water heater work on a generator?
Neither the A.O. Smith nor the Rheem manual cited here mentions generators, outages or UPS units. What they do require is a grounded 120 V supply, no GFCI, and no extension cord, and A.O. Smith adds that the heater is polarity sensitive. A generator feeding the heater through a transfer switch, set up by an electrician, meets those rules best.
Can I still get hot water from a power vent heater during an outage?
Yes, for a while. The burner stops, but the water already heated stays in the insulated tank, and city water pressure still pushes it out. A 50 gallon tank holds about 49 gallons. Once that is used, the incoming cold water is not reheated until power returns. Homes on a well lose pressure too.
How many amps does a power vent water heater draw?
The nameplate figures are about 5 A: A.O. Smith lists 120 V and 5 amps for the GPVL-50, and Rheem gives a maximum current draw of approximately 5.0 amps. Those are ceilings. A replacement exhaust blower motor sold for A.O. Smith heaters is rated 1.8 A at 115 V, so the running draw is likely well below 5 A. Measure it with a plug-in meter.
Why does my power vent heater try to light three times and then stop?
That is the ignition control giving up. Rheem says the control makes three trials for ignition before going into lock-out. A.O. Smith's service handbook lists a 20 minute soft lockout after the retry limit. On a UPS, a heater that keeps doing this may be failing to sense flame on a stepped (simulated sine) output. Try a pure sine UPS.
Should I replace my power vent heater with one that works without power?
Only if your venting allows it, and a plumber has to decide that. An atmospheric vent relies on hot exhaust rising up a flue on its own, so it cannot simply reuse the plastic pipe a blower pushes through a wall. Where it fits, a millivolt gas control such as Bradford White's ICON needs no external electricity.
Sources and further reading
- A.O. Smith: ProLine XE 50 Gallon Power Vent, GPVL-50 200, specifications
- A.O. Smith: Installation and Operating Manual, Residential Gas Water Heaters, Power Vented Gas Models with Hot Surface Ignition, Series 200/201
- A.O. Smith: Service Handbook, Power Vented Gas Models with Hot Surface Ignition (322153-000)
- Rheem: Use & Care Manual, Residential 40, 50 and 60 Gallon, Canadian edition (AP22548 Rev 01)
- Rheem: Use & Care Manual, Residential 75 Gallon power vent (AP22670)
- Rheem: Performance ENERGY STAR Power Vent specification sheet (THD-PGPV N Rev. 9)
- Electric Motor Warehouse: A.O. Smith water heater exhaust blower 183381-000, motor ratings
- Bradford White: ICON System gas control sell sheet (IGV-SS 0915)
- APC by Schneider Electric FAQ000210003: Back-UPS No-load Shutdown