Can You Put a Septic Aerator on a UPS?

Yes, if your aerobic system uses a linear diaphragm air pump. Hiblow and Secoh rate theirs at 51 to 100 W, and a common 1500 VA tower runs one for roughly 1 to 2 hours. That keeps air in the tank through a typical short outage, but it does not keep the system draining: the spray or dose pump draws around 9 A, and extension guidance for every outage still starts with using less water.

On this page
  1. What the aerator draws, by type
  2. How long a UPS runs a linear aerator
  3. Bacteria or water level: what an outage actually threatens
  4. Why the effluent pump stays off the UPS
  5. Wiring it up safely
  6. What to do instead of, or as well as, a UPS
  7. Where this answer stops applying
  8. Frequently asked questions

An aerobic treatment unit (ATU) is the one kind of septic system that stops working when the power goes out. Oklahoma State University's extension fact sheet lists two things it needs electricity for: "the aerator, which supplies air to the aeration chamber and the pump that disposes the treated effluent to the dispersal area." Those two loads differ by an order of magnitude, and that difference decides what a UPS can do for you. It can carry the aerator. It cannot carry the pump.

What the aerator draws, by type

Residential ATUs get their air from one of three kinds of machine. The data sheets publish different things for each, and the gap between them is the first thing to check before buying anything.

Published electrical ratings for common septic aerators and one effluent pump
UnitTypePublished ratingVolts x ampsSheet says it fits
Hiblow HP-60Linear diaphragm51 W, 1.3 A at 120 V156 VANot stated
Secoh EL80ALinear diaphragm61 W, 2.6 A at 115 V299 VANot stated; "UL Rated for Outdoor Use"
Hiblow HP-80 and HP-80A (alarm)Linear diaphragm71 W, 1.6 A at 120 V192 VAMany 500 and 600 GPD systems
Hiblow HP-120LLLinear diaphragm100 W, 1.4 A at 120 V168 VAMany 750 GPD and some 1000 GPD systems
Gast 0523Rotary vane, 1/4 HP4.7 A at 120 V (watts not stated)564 VAMany 500, 600 and 750 GPD systems
Norweco Singulair 225LSubmerged motor, 1/6 HP4 A at 115 V (watts not stated)460 VANorweco Singulair Green
Little Giant 10ECH (effluent pump, for scale)Submersible, 1/2 HP9.0 A at 115 V1,035 VASeptic tanks or aerobic systems

The linear pumps are small loads for any UPS. A 1/4 HP rotary vane compressor and Norweco's motor aerator sit in a different class: their sheets give amps and horsepower but no watts, and the volts-times-amps figure is a ceiling, not a running number. The Norweco sheet adds one figure that helps: the 225L is "ANSI/NSF certified to operate only 30 minutes per hour", so its average draw is half its running draw.

Our analysis: amps overstate linear pumps by 1.7 to 4.9 times

On every linear pump sheet above, volts times amps comes out far above the published watts: 156 VA against 51 W for the HP-60, 192 VA against 71 W for the HP-80, 168 VA against 100 W for the HP-120LL, and 299 VA against 61 W for the EL80A. The sheets do not say how the amps were measured, so we cannot tell whether the gap is the pump's power factor or a conservative label figure. Either way, the practical rule is the same as for any load (see VA vs watts): use the watts for runtime and check the VA against the UPS's VA rating. Even the EL80A's 299 VA fits inside a 600 VA unit.

How long a UPS runs a linear aerator

These estimates use the model behind our UPS runtime calculator: new sealed lead-acid batteries, a Peukert exponent of 1.25 referenced to the 20-hour rating, 88% inverter efficiency and 8 W of inverter overhead. Battery sizes are typical for each class. Why UPS runtime is not linear explains each term.

Estimated continuous runtime by aerator and UPS class (new batteries, room temperature)
UPS class (battery)HP-60, 51 WEL80A, 61 WHP-80, 71 WHP-120LL, 100 W
600 VA (1 x 12 V 7 Ah, 84 Wh)38 min31 min26 min18 min
850 VA (1 x 12 V 9 Ah, 108 Wh)51 min42 min36 min24 min
1000 VA (2 x 12 V 7 Ah, 168 Wh)1 h 29 min1 h 14 min1 h 2 min42 min
1500 VA (2 x 12 V 9 Ah, 216 Wh)2 h 2 min1 h 41 min1 h 25 min58 min
2200 VA (2 x 12 V 18 Ah, 432 Wh)4 h 51 min3 h 59 min3 h 22 min2 h 17 min

Here is the arithmetic for an HP-80 on a 1500 VA tower. The battery supplies the pump plus overhead, divided by inverter efficiency:

Battery draw = (71 W + 8 W) / 0.88 = 89.8 W, or 3.74 A at 24 V
Runtime = 20 h x (9 Ah / (3.74 A x 20 h))^1.25 = about 1.42 h, or 1 h 25 min

The table assumes the pump runs the whole time; if your panel cycles it on a timer, runtime stretches in proportion. These are new-battery figures, so an aging battery gives less, and the alarm panel and any timer add load if they share the UPS. For anything beyond a couple of hours, the options are extended battery packs or a generator.

Rotary vane and motor aerators

Without published watts, a table for these would be guesswork. What can be bounded is the worst case. If the Norweco 225L drew its full 460 VA as watts, a 1500 VA tower would give about 9 minutes of motor time; at 30 minutes per hour, that is roughly 18 minutes of clock time. Its real watts are lower, so real runtime is longer, but by how much only a meter can say. Measure the running draw with a plug-in meter (how to measure power draw), then test the UPS starting the motor on battery several times. Neither sheet publishes starting current, and a motor that trips the UPS at start produces the overload alarm instead of air.

Bacteria or water level: what an outage actually threatens

Two answers circulate. One says the aerobic bacteria die within hours without air, so the aerator must never stop. The other says an ATU shrugs off an outage. The extension fact sheets support neither, and they point at a different problem.

On the biology, Oklahoma State's line is drawn at days, not hours. After "a long power outage (i.e., more than three days)," it says, the aerobic bacterial community's numbers "significantly decrease under anaerobic conditions," and "it will take a couple of days" to recover. For an outage of a few hours, the same fact sheet's advice is only to check, once power returns, that the aerator is humming, and to reset the dispersal timer.

On the plumbing, the clock is much shorter. Texas A&M AgriLife Extension explains that electrical components "usually have a reserve or alarm capacity that allows some use during electrical power outages," but that "the minimum required reserve capacity in Texas is one-third of the daily design flow. Thus, a three-bedroom home would have a reserve capacity of only 80 gallons." One-third of a day is about eight hours' worth of the system's design flow. Hamilton County Public Health in Ohio states the consequence directly: "Aerobic treatment units will discharge untreated wastewater if used heavily or for extended periods during a power outage."

Bottom line

A UPS on a linear aerator keeps air in the tank for one to two hours, which covers the short outages that are least likely to harm the bacteria in the first place. It does nothing for the risk that arrives first in a long outage, a tank filling with no pump to empty it. That is why every extension source here starts with cutting water use, not with backup power for the aerator. Buy the UPS for convenience, never as a substitute for the water rules.

Why the effluent pump stays off the UPS

The dose or spray pump that moves treated water to the field is the load a UPS would need to keep the system draining, and it is far beyond one. The Little Giant 10ECH, a 1/2 HP high head effluent pump sold for septic and aerobic systems, runs at 9.0 A at 115 V, about 1,035 VA, before any starting surge. That is the same problem the sump pump guide works through: running watts near a desktop UPS's limit, a starting demand above it, and a duty cycle that empties a small battery in minutes. A well pump is the extreme version.

The pump also does not run continuously. Texas A&M notes that "a time-dosed system may take 24 hours for all of the stored water to be distributed and the high-water alarm to be deactivated" after power returns, and warns that on an on-demand system "the first dose after power is restored can overload your system." Neither problem is one a battery solves.

Wiring it up safely

Oklahoma State describes the usual layout: "The aerator (or air pump) and the electronic panel/timer are usually housed in a control box on the land surface just above the aeration tank." A desktop UPS belongs indoors, dry and ventilated (where to place a UPS), so the question is how power gets from it to that box.

  • Cord-and-plug air pump. The simplest case, but the UPS can feed the pump only through wiring and receptacles rated for an outdoor, wet location. An indoor extension cord run across the yard does not qualify.
  • Hardwired control panel. Splicing a cord into a hardwired septic panel is electrician work. The clean routes are an inlet with a transfer switch, or a hardwired UPS; hardwired vs plug-in UPS compares them.
  • Flood risk. Oklahoma State says to turn an ATU off if the control box is likely to be submerged, because the aerator and panel "could short-circuit if powered when they are flooded." A UPS keeps that box live after you cut the house breaker, so switch the UPS off too.

Choose a pure sine wave UPS. None of these sheets states a waveform requirement, but linear pumps drive a diaphragm with an electromagnet at line frequency, the same kind of mechanism the aquarium guide describes buzzing and running hot on a stepped wave, and Norweco describes the 225L's motor as split phase.

What to do instead of, or as well as, a UPS

  1. Cut water use the moment the power fails. Texas A&M: for an outage under a day, "limit water usage to essentials such as toilet flushing and hand washing" with no laundry, bathing, showers or dishwashing; for an extended outage, "stop all water use." Oklahoma State: past three days, "water should no longer be disposed down the drain."
  2. For long outages, power the whole system. Oklahoma State's advice is direct: "If available, use a backup electricity generator to power the system." Size the generator for the effluent pump's start plus the aerator. UPS vs generator sets out the trade-off, and using a UPS with a generator covers running both.
  3. After power returns, check and wait. Listen for the aerator, reset the dispersal timer, and keep laundry and long showers down for a day after an outage longer than a day (Texas A&M), or three days after one longer than three days (Oklahoma State). Hamilton County expects alarms that "could continue for several hours, even if reset."
  4. Keep a spare air pump. LSU AgCenter notes that "blowers on septic units must be periodically replaced" and suggests having one on hand. A failed pump stops the system as completely as an outage, and no UPS fixes that.

Where this answer stops applying

  • Other aerators. The figures are for the Hiblow, Secoh, Gast and Norweco units named. Other brands and larger commercial blowers need their own sheets, or a meter.
  • Other states' rules. The 80-gallon reserve is Texas's minimum. Your system's reserve depends on its design and your state's code; your service provider can tell you what it holds.
  • 230 V systems. Hiblow states that 230 VAC CE compliant models exist, but every rating here is the 115 to 120 V version.
  • Systems that are not ATUs. Oklahoma State notes that a conventional gravity septic system "does not require electricity and is not affected by power outages." Pumped systems without aeration, such as dosed mounds or drip fields, have only the pump problem, which a UPS does not solve.

Frequently asked questions

How many watts does a septic aerator use?

A linear diaphragm air pump, the common type on residential aerobic systems, uses 51 to 100 W by the makers' sheets: Hiblow HP-60 51 W, Secoh EL80A 61 W, Hiblow HP-80 71 W, HP-120LL 100 W. Rotary vane compressors and submerged motor aerators publish amps instead: 4.7 A for a Gast 0523, 4 A for a Norweco 225L. Those are larger loads, and the only way to get their watts is to measure.

How long can an aerobic septic system go without power?

Oklahoma State University Extension treats more than three days as a long outage: after one, the aerobic bacteria have significantly decreased and need a couple of days to recover, so water use should stay low for three more days. The shorter limit is hydraulic. Texas A&M notes the minimum reserve capacity in Texas is one-third of daily design flow, 80 gallons for a three-bedroom home.

Will a battery backup keep my septic alarm from going off?

Only if the alarm and its panel are on the UPS too, and only for as long as the battery lasts. The high-water alarm can still sound when power returns if water was used during the outage, because the dose or spray pump was off. Texas A&M says a time-dosed system may take 24 hours to clear the stored water and silence the alarm.

What size generator do I need for an aerobic septic system?

Add the aerator's running watts to the effluent pump's starting demand, since the pump is the large load. A 1/2 HP effluent pump such as the Little Giant 10ECH runs at 9.0 A, about 1,035 VA at 115 V, and needs more for a moment at start. Oklahoma State recommends a backup generator for the system if one is available during an outage.

Can I run my septic aerator off a solar panel or car battery?

The air pumps listed here are 115 to 120 V AC motors, so a battery needs an inverter in between, which is what a UPS already is. A 12 V battery with a pure sine inverter can run a 51 to 71 W linear pump for hours if the battery is large enough. Keep the battery and inverter dry and ventilated, and follow the inverter maker's wiring instructions.

Sources and further reading

  1. Specifications for Hiblow HP-60 unit (spec sheet PDF)
  2. Specifications for Hiblow HP-80 unit (spec sheet PDF)
  3. Specifications for Hiblow HP-80A alarm unit (spec sheet PDF)
  4. Specifications for Hiblow HP-120LL unit (spec sheet PDF)
  5. Specifications for Secoh EL80A (spec sheet PDF)
  6. Gast 0523 rotary vane septic air pump specification sheet (SepticSolutions)
  7. Norweco: Singulair Green Low Profile System, Model 225L aerator
  8. Little Giant 10ECH-CIA-RF 1/2 HP high head effluent pump (SepticSolutions)
  9. Lesikar, O'Neill and Smith, Texas A&M AgriLife Extension: Onsite Wastewater Treatment Systems: Responding to Electrical Power Outages and Floods (ER-001)
  10. Abit and Walker, Oklahoma Cooperative Extension Service: Septic Systems, What to do after Severe Weather (PSS-2920, April 2019)
  11. Hamilton County (Ohio) Public Health: Household Sewage Treatment Systems and Power Outages
  12. LSU AgCenter: Navigating Floods and Power Outages for Septic Systems