Can I Use a Car Battery or Deep-Cycle Battery With My UPS?

Yes, electrically it works: a UPS will run from any lead-acid battery of the right voltage. But its charger is sized for the 7 to 9 Ah battery inside, so a 100 Ah battery can take three days to more than a week to refill, and a flooded car battery vents hydrogen while it charges. A UPS with an external battery pack connector is the supported way to get more runtime.

On this page
  1. The terms this answer turns on
  2. First, match the voltage
  3. Worked through: a 100 Ah bank on an APC BX1500M
  4. Five UPS models, worked out for 100 Ah
  5. Why a flooded car battery needs venting
  6. The inverter is built for minutes
  7. What it does to the warranty
  8. The supported route: a UPS built for packs
  9. What people who do it anyway report
  10. What this answer does not cover
  11. Frequently asked questions

Short version: the UPS does not care where its DC power comes from. A big battery of the right voltage will run it. The trouble starts after the outage, when the UPS has to put that energy back. It also starts in the room, if the battery is the flooded kind.

The terms this answer turns on

Three kinds of lead-acid battery get mixed up in this question.

  • Car (starting) battery: built to give a very large current for a few seconds to crank an engine. The alternator then tops it up right away. Most are flooded: the plates sit in liquid acid, and the case has vents. That makes them the unsealed type.
  • Deep-cycle battery: built to be drained a long way and recharged many times, as in boats, RVs and solar setups. It can be flooded, AGM or gel.
  • UPS battery: almost always a sealed VRLA AGM block, such as 12 V 9 Ah. It sits on float charge for years and gives a few minutes of high current. See UPS battery types for how they differ.

Two more terms. Recharge time is how long the UPS takes to refill its battery after an outage, and makers publish it. An external battery pack is a box of batteries the UPS maker builds for one product family. It plugs into a dedicated DC connector on the back of the UPS.

First, match the voltage

A UPS's battery voltage is fixed. APC's manual for the Back-UPS Pro BX850M through BX1500M gives it plainly. The two small models use one 12 V battery. The BX1350M and BX1500M use "24V with 2 batteries." The BR1500G is also 24 V. The Smart-UPS X SMX1500RM2U runs a 48 V cartridge.

So one car battery only fits a 12 V UPS. A 24 V UPS needs two matched 12 V batteries in series, and a 48 V unit needs four. One 12 V battery on a 24 V UPS will not run it. If you are not sure what your unit uses, the replacement cartridge label tells you; see battery sizes and terminals.

Worked through: a 100 Ah bank on an APC BX1500M

Take a BX1500M, a common 1500 VA, 900 W tower. Its datasheet lists a 24 V lead-acid battery, cartridge APCRBC124, which Schneider rates at 24 V 9 Ah. It gives a typical recharge time of 16 hours.

Now suppose you swap in two 12 V 100 Ah deep-cycle batteries in series. That makes a 24 V 100 Ah bank. The charger is the same charger, so the time grows with the amp-hours:

New recharge time approx. = Published recharge time x (New Ah / Stock Ah)
  • Capacity ratio: 100 Ah / 9 Ah = 11.1
  • Recharge time: 16 h x 11.1 = about 178 hours, or 7.4 days
  • Stored energy: 24 V x 100 Ah = 2,400 Wh, against 216 Wh for the stock cartridge

The datasheet also lists a rated battery charging power of 11 W. Divide 2,400 Wh by 11 W and you get about 218 hours. That is roughly nine days, before any charging losses. The two figures agree on the scale. The battery is empty for more than a week after one long outage.

That is the hidden cost. A storm that knocks the power out twice in three days meets a battery that is maybe half full. A lead-acid battery that is left part-charged also ages faster, as covered in storing a UPS and batteries.

Five UPS models, worked out for 100 Ah

The same arithmetic, run on figures each maker publishes. The 100 Ah column assumes a bank of 100 Ah blocks at the UPS's own voltage.

Published recharge time scaled to a 100 Ah bank (straight-line estimate)
ModelStock batteryPublished recharge100 Ah estimatePack connector
APC BX850M12 V 9 Ah (RBC17)12 habout 133 h (5.6 days)None on rear panel
APC BX1500M24 V 9 Ah (APCRBC124)16 habout 178 h (7.4 days)None on rear panel
APC BR1500G24 V 9 Ah (APCRBC124)8 habout 89 h (3.7 days)Yes, BR24BPG
CyberPower CP1500PFCLCDTwo 12 V 9 Ah (24 V)8 habout 89 h (3.7 days)None listed (0 EBMs)
APC SMX1500RM2U48 V 9 Ah (APCRBC115)3 habout 33 h (1.4 days)Yes, SMX48RMBP2U

Look at the charger, not the VA rating. The BX1500M and BR1500G are both 1500 VA with the same cartridge. Yet APC rates their charging power at 11 W and 23 W. That is why one takes twice as long as the other. The Smart-UPS X lists 103 W.

The BX1500M and BR1500G are easy to confuse by name. Only the BR1500G manual lists an "External Battery Pack connector" on its rear panel. The BX-M manual lists outlets, data and Ethernet ports, a wiring fault light and a circuit breaker. It shows no battery connector.

Why a flooded car battery needs venting

Lead-acid batteries give off hydrogen while charging. Hydrogen is explosive in air. A sealed AGM block recombines most of that gas inside. A flooded car battery lets it out through its vents.

OSHA's construction-industry rule on batteries, 29 CFR 1926.441(a)(1), says "Batteries of the unsealed type shall be located in enclosures with outside vents or in well ventilated rooms." The next paragraph requires ventilation "to ensure diffusion of the gases from the battery." The rule is written for job sites, not homes. The gas is the same either way.

A UPS charger keeps a battery on float charge all day, every day. So a flooded battery beside a desk is a small hydrogen source that never switches off. And it sits in a room nobody planned to ventilate. One owner wrote up a home battery bank on digdilem.org. They put it bluntly: "Lead acid batteries emit more hydrogen when charging than SLA batteries do, which is explosive. Ensure your space is well ventilated."

The inverter is built for minutes

Our analysis: the stock battery is also a timer

On battery, the inverter turns DC into AC. Part of that power ends up as heat inside the case. With a 216 Wh cartridge, the battery runs out long before that heat matters. With a 2,400 Wh bank, nothing ends the run but the load or the UPS's own heat protection. The BR1500G manual lists fault codes F07 "Temperature" and F08 "Fan Event". CyberPower's OL manual covers the same case. When the high-temperature sensor trips, the UPS "generates an alarm and shuts down." Those are safeguards, not a rating for hours of use. Neither maker publishes a continuous on-battery time for a desktop unit with a bank it never sold.

A big battery also changes the fault current. The BR1500G manual already warns that a battery "can present a risk of electric shock and burns by high short-circuit current." A 100 Ah bank can push far more current into a cable fault than a 9 Ah cartridge. The digdilem build includes a thermal cutout fuse. Its author also says to use heavier cable where the wiring is long, to avoid voltage drop.

What it does to the warranty

APC's answer is short. Its FAQ on battery cartridges says: "The use of modified or third party replacement batteries voids any remaining manufacturers warranty, the Equipment Protection Policy, and the UL or CE certification of the UPS System." The BR1500G manual adds that batteries should be replaced "with the same number and type of batteries as originally installed."

CyberPower's Smart App Online manual says to "Only use replacement batteries which are certified by CyberPower Systems." It calls the wrong battery type "an electrical hazard that could lead to explosion, fire, electric shock, or short circuit." So a car battery does more than void a warranty. It ends the connected-equipment cover and the safety listing too. For ordinary replacement blocks, see OEM vs aftermarket UPS batteries.

The supported route: a UPS built for packs

An extended-runtime UPS has a pack connector and a pack the maker has matched to it. Here is what the makers list.

Pack-capable models and what the maker publishes
UPSInternal batteryPackRecharge
APC BR1500G (1500 VA / 865 W)24 V 9 AhBR24BPG: 24 V 18 Ah, 372 VAh8 h stock; about 24 h with one pack by the same scaling
APC SMX1500RM2U (1440 VA / 1200 W)48 V 9 AhSMX48RMBP2U: 48 V, 864 VAh3 h stock; about 9 h with one pack by the same scaling
CyberPower OL1500RTXL2U (1500 VA / 1350 W)Three 12 V 9 Ah (36 V)BP36V60ART2U, up to 10 EBMs4 h to 90%, which CyberPower says holds "regardless of the number of EBMs"

The BR1500G row shows the pack route still costs recharge time. 27 Ah in total is three times the stock battery, so 8 hours becomes about 24. But the pack is sealed, fused and listed for that UPS. The CyberPower row is the better pattern. Its Fast Charge feature is built to hold the recharge time flat as modules are added. The OL manual has a menu setting, "EBM Number", from 0 to 10, for telling the UPS how many modules are attached.

How much runtime a pack adds is worked out in extended runtime battery packs. Doubling capacity more than doubles runtime, for reasons covered in UPS runtime explained. To find a pack-capable model by name, the suffixes are decoded in how to read UPS model numbers.

What people who do it anyway report

The digdilem.org write-up is a fair picture of the careful version. The owner wired four sealed SLA batteries into an APC Smart-UPS 750. They used 2S2P: two in series for 24 V, and two such strings in parallel. They report it runs "a little NAS" for "around half a day without mains power." They also note the cost. A bigger bank "will obviously take longer" to recharge.

Note what that build is not. It uses sealed batteries, not a flooded car battery. It runs a light load. It sits on a business-class Smart-UPS, not a budget desktop unit. Even so, it still voids the warranty and the listing, as above.

What this answer does not cover

The recharge figures here are straight-line estimates from published numbers. Real chargers slow down near full, so a real bank can take longer. Nothing here replaces your model's manual. It does not cover lithium conversions either. Those need a UPS designed for them; see lithium UPS pros and cons. It does not cover large three-phase UPS systems with battery cabinets, or the building and fire codes for battery rooms. For many hours on a small load, a portable power station may suit better; see UPS vs portable power station. If any battery near your UPS has swollen or leaks, stop and read swollen UPS battery first.

Bottom line

A car or deep-cycle battery will run a UPS. But a desktop charger built for 9 Ah needs roughly 4 to 7.5 days to refill 100 Ah. A flooded battery needs real ventilation, and the change voids APC's warranty, its Equipment Protection Policy and the UL listing. If you need more runtime, buy a UPS with a pack connector and the maker's pack.

Frequently asked questions

Will my UPS charge a 100 Ah battery at all?

It will try. The charger pushes the same small current it always does, so the battery fills slowly. Scaling from the published figures, an APC BR1500G or CyberPower CP1500PFCLCD (8 hours for 9 Ah) needs about 89 hours for 100 Ah, and a BX1500M (16 hours) about 178 hours. A second outage in that window finds a part-charged battery.

Is an AGM car battery safer than a flooded one on a UPS?

On gas, yes. An AGM battery is sealed and valve regulated, like the battery the UPS shipped with, so it does not fall under the unsealed-battery venting rule the way a flooded battery with vent caps does. It does not fix the slow charger, the inverter heat, the short-circuit current of a big battery or the void warranty.

Can I connect a 12 V car battery to a 24 V UPS?

No. A 24 V UPS such as the BX1500M or BR1500G expects two 12 V batteries in series. One 12 V battery gives half the voltage it needs, and it will not run. You would need two matched batteries of the same type, size and age wired in series.

Can I use a LiFePO4 deep-cycle battery instead?

Not on a UPS built for lead-acid. CyberPower's manual says to use only batteries it certifies and that the wrong battery type "is an electrical hazard that could lead to explosion, fire, electric shock, or short circuit." A lead-acid charger also does not speak to a lithium battery's management system. Buy a UPS designed for lithium instead.

How do I know if my UPS takes an external battery pack?

Look for a battery pack connector on the rear panel and a pack model in the datasheet. The APC BR1500G manual lists an "External Battery Pack connector". The BX1500M manual shows no battery connector at all. CyberPower lists the compatible module and the maximum count on the product page.

Sources and further reading

  1. OSHA 29 CFR 1926.441, Batteries and battery charging
  2. APC BX1500M product page, datasheet and Back-UPS Pro BX850/1000/1350/1500M user manual (Schneider Electric)
  3. APC BR1500G product page, datasheet and user manual JPW027994 (Schneider Electric)
  4. APC BR24BPG Back-UPS Pro External Battery Pack datasheet (Schneider Electric)
  5. APC Smart-UPS X SMX1500RM2U datasheet, with APCRBC115 and SMX48RMBP2U datasheets (Schneider Electric)
  6. APC FAQ: Can I change the individual batteries inside of a Back-UPS replacement battery cartridge?
  7. CyberPower OL1500RTXL2U specifications and Smart App Online UPS user manual
  8. CyberPower CP1500PFCLCD specifications
  9. digdilem.org: UPS expansion (owner write-up, Smart-UPS 750 with a 2S2P battery bank)