Usually not. When the fan stops, radon can climb back toward its old level within hours. But the risk from radon builds over years, not over one evening. So a short outage matters little, and a long one is more than a battery can cover anyway. The question is less "will the fan stop?" and more "for how long?"
A small fan is easy to carry. A common 1500 VA UPS runs a 15 to 21 W RadonAway RP140 for 5 to 6.5 hours. A big fan is another matter: the same UPS runs a 310 W Festa Eagle for about 15 minutes.
What a radon fan does
Most radon systems in homes with a basement or slab use soil suction. Pennsylvania's radon guide describes the usual version, active sub-slab suction. One or more pipes go through the floor slab into the gravel or soil beneath. A radon vent fan on the pipe "draws the radon gas from below the house and releases it into the outdoor air." At the same time it holds a slight vacuum under the slab, so soil gas is pulled away from the house instead of seeping in.
"Active" means the system has a fan. A passive system relies on natural air currents instead. Pennsylvania calls passive suction "generally not as effective in reducing high radon levels" as the active kind. That is why the fan matters in an outage. Without power, an active system becomes a passive one.
The fan usually sits outside the living space. Pennsylvania lists "unconditioned house and garage spaces, including attics and the exterior of the house" as common spots. That matters for a UPS, as you will see below.
In a basement with a sump, Pennsylvania notes the sump pit can be capped and used as the suction point. The sump pump then becomes a second outage question in the same corner of the house, and a much larger load.
How fast radon comes back when the fan stops
Fantech, which makes radon fans, puts it plainly: "If you turn the radon fan off, the radon gas level may return to pre-mitigation levels within a few hours." So the rebound is quick. Within an evening, a home can be back near the level that led to the system in the first place.
Pennsylvania's guide gives a related figure for a different case. When a home lowers radon by opening windows and vents, and then closes them, radon "most often" returns to its old level "within about 12 hours." That is not a fan outage, but it shows the same time scale: hours, not weeks.
None of the agency pages read for this article mentions power outages. Not EPA's page on checking a system, not Pennsylvania's guide and not South Carolina's or Ohio's. So no agency sets a safe length for an outage. That gap is part of why the question gets two answers.
Why a short outage matters less than a long one
Radon is a long-term risk. Ohio's health department says exposure to high radon "over the course of your lifetime increases your risk of developing lung cancer." Pennsylvania bases its advice on a long-term test, or on the average of two short-term tests. It says a long-term test "will give a better understanding of your home's year-round average radon level."
Read together, the agencies judge a home on its average over months, not on one bad day. A few hours at the old level is a small part of that average. A week without power is a much bigger part. Pennsylvania also says "any radon exposure has some risk of causing lung cancer," so a short outage is not harmless. It is just small next to the years the system runs.
One more point follows from Fantech's wording. The fan's job is to hold radon below the pre-mitigation level. So the higher your home tested before the system went in, the more an outage brings back. A home that tested just above 4 pCi/L (picocuries per liter, the unit radon is measured in) has less to lose than one that tested at 20.
How many watts radon fans draw
Radon fans are small, steady loads. They run all day, every day, and they draw about the same power the whole time. The makers list a range, because the draw depends on how hard the fan has to pull. Minnesota's health department explains it: "The less air a fan moves, the less electricity used."
| Fan | Catalog watts | Minnesota max watts | Duct |
|---|---|---|---|
| RadonAway RP140 | 15 to 21 | 19 | 4 in |
| RadonAway RP145 | 41 to 72 | 66 | 4 in |
| RadonAway RP260 | 50 to 75 | 65 | 6 in |
| RadonAway RP265 | 91 to 129 | 136 | 6 in |
| RadonAway RP380 | 95 to 152 | 138 | 8 in |
| RadonAway GP201 | 40 to 60 | Not listed | 3 in |
| RadonAway GP501 | 70 to 140 | 146 | 3 in |
| Festa AMG Maverick | 66 | 66 | 4 in |
| Festa AMG Eagle | 310 | 310 | 3 in |
The two lists mostly agree, but not always. Minnesota lists the RP265 at 136 W and the GP501 at 146 W, both above the top of RadonAway's own range. That is reason enough to measure your own fan with a plug-in watt meter, as Minnesota suggests. Our guide to measuring power draw shows how. The Eagle stands out: it is a high-suction fan for tight soils like clay, and it draws nearly five times what a 66 W Maverick does.
Runtime on a UPS, by fan
A UPS (uninterruptible power supply) is a battery and inverter that takes over the moment the power fails. The estimates below use the model in our UPS runtime calculator: new sealed lead-acid batteries, 88% inverter efficiency and 8 W of UPS overhead. Why UPS runtime is not linear explains each term. Each range runs from the fan's highest catalog watts to its lowest.
| Fan (catalog watts) | 1500 VA / 900 W (2 x 12 V 9 Ah) | 2200 VA (2 x 12 V 18 Ah) | Energy per day |
|---|---|---|---|
| RP140 (15 to 21 W) | 5 h to 6 h 38 min | 11 h 48 min to 15 h 46 min | 0.36 to 0.50 kWh |
| GP201 (40 to 60 W) | 1 h 43 min to 2 h 38 min | 4 h 4 min to 6 h 17 min | 0.96 to 1.44 kWh |
| RP145 (41 to 72 W) | 1 h 24 min to 2 h 34 min | 3 h 19 min to 6 h 7 min | 0.98 to 1.73 kWh |
| RP260 (50 to 75 W) | 1 h 20 min to 2 h 5 min | 3 h 10 min to 4 h 58 min | 1.20 to 1.80 kWh |
| Maverick (66 W) | 1 h 32 min | 3 h 39 min | 1.58 kWh |
| GP501 (70 to 140 W) | 39 min to 1 h 26 min | 1 h 32 min to 3 h 25 min | 1.68 to 3.36 kWh |
| RP265 (91 to 129 W) | 43 min to 1 h 4 min | 1 h 42 min to 2 h 33 min | 2.18 to 3.10 kWh |
| RP380 (95 to 152 W) | 35 min to 1 h 1 min | 1 h 24 min to 2 h 25 min | 2.28 to 3.65 kWh |
| Eagle (310 W) | 15 min | 35 min | 7.44 kWh |
The last column is the fan's watts times 24 hours. It is the number to use for a portable power station or a generator, which is where multi-day backup comes from. No tower UPS carries even the smallest fan through a full day.
Worked through: an RP145 in an 8-hour outage
Take an RP145, the 4-inch fan in the middle of RadonAway's range. Suppose it shares nothing, sits on a 1500 VA / 900 W tower, and the power fails at 6 pm for 8 hours.
1500 VA runtime: about 1 h 24 min at 72 W, 2 h 34 min at 41 W
Fan stops: roughly 7:30 to 8:30 pm
Hours without the fan: about 5.5 to 6.5 of the 8
By Fantech's figure, radon may be back near its old level a few hours after the fan stops. So in this case the UPS delays the rebound but does not prevent it. The house spends the back half of the night at or near its pre-mitigation level either way.
Now swap in a 2200 VA unit with 18 Ah batteries. The same fan runs about 3 h 19 min to 6 h 7 min. At the low end of the fan's draw, that covers most of the outage. At the high end it covers less than half. Which end your fan sits at is the thing to measure before you buy.
Finally, put an Eagle on the 1500 VA tower. It runs about 15 minutes. That is not backup in any useful sense. A fan that size needs a generator or nothing.
The trap: a fan that draws too little
APC says Back-UPS models with No-load Shutdown turn off "while operating on battery power when the attached load is less than 15 watts," after 15 minutes. RadonAway lists the RP140 at 15 to 21 W, so at its low end it sits right on that line. If the UPS shuts itself off, the fan stops 15 minutes into the outage instead of 5 hours in. Check your UPS manual for the feature and turn it off.
The two answers you will find, and which is right
One answer says the fan must never stop, so it needs backup. It quotes the agencies. South Carolina's sheet says "The fan should NEVER be turned off; it must run continuously for the system to work correctly." Pennsylvania's guide says the same.
The other answer says radon is a slow, long-term risk, so outages do not matter. Both are half right.
The "never off" rule is about how the system works. It tells owners not to switch the fan off. It does not mention outages, and no agency page here does. The long-term answer is closer to how the agencies judge risk, by averages over months. But Fantech's rebound figure means a long outage is not free. Days at the old level are days of the exposure the system was built to stop.
Bottom line
For outages of a few hours, backup is optional. A 1500 VA UPS covers the first 80 minutes to 2.5 hours for fans up to about 75 W, and 5 hours or more for an RP140. It is not worth it for a fan as large as the Eagle. For outages that run a day or more, a UPS is too small. A generator or power station sized from the fan's daily kWh is the tool.
Setting it up
- Check how the fan is wired. RadonAway's GP fans come with an "electrical box for hard wire or plug in." A hardwired fan cannot plug into a UPS. Changing that is electrical work, and Pennsylvania says radon system wiring must follow local electrical codes. See hardwired vs plug-in UPS.
- Find a spot for the UPS. The fan is often in an attic, a garage or outside. A UPS battery does not like heat or cold, and our guide to where to place a UPS covers why. Put the UPS where the fan's cord reaches it, in the most stable spot you can.
- Measure the fan. Plug it into a watt meter for a few minutes and note the reading. Use that figure in the runtime calculator.
- Turn off No-load Shutdown if your UPS has it and the fan draws near 15 W.
- Test it. Switch off the breaker and watch the U-tube gauge on the radon pipe. The liquid should stay offset while the fan runs on battery. None of the catalogs states a waveform need, but a pure sine UPS removes the question; see pure sine vs simulated sine.
- Check the gauge after every outage. When the power returns, confirm the fan is pulling again. If your alarm has an outage delay, like the 99-hour setting on Festa's battery gauge, set it so a real fault still gets noticed.
Keep the rest of the system's care as it was. EPA says fans "may last for five years or more" and that a replacement costs "around $200 - $350 including parts and labor." It also suggests retesting "at least every two years." If your home was without power for days, the next scheduled test is a fair time to check the system is back to normal.
What this answer does not cover
These figures come from the makers' catalogs and Minnesota's list. Your fan's label, and a meter reading, govern. The runtimes assume new batteries at room temperature. A UPS in a cold garage or a hot attic will fall short of them. Nothing here says how much a given outage adds to anyone's risk. No source read for this article puts a number on that, and a radon professional or your state radon program is the place to ask. Systems with more than one fan, and ventilation-based systems such as heat recovery ventilators need their own figures. If your fan is hardwired, any change to its wiring is a job for an electrician.
Frequently asked questions
How many watts does a radon fan use?
Most residential fans use between 15 and 150 W. RadonAway's catalogs list the RP140 at 15 to 21 W, the RP145 at 41 to 72 W, the RP265 at 91 to 129 W and the GP501 at 70 to 140 W. Festa lists the Maverick at 66 W and the Eagle at 310 W. Minnesota's health department says a fan that moves less air uses less power, so a plug-in watt meter gives your real figure.
How fast does radon come back when the fan stops?
Fantech says radon "may return to pre-mitigation levels within a few hours" once the fan is off. Pennsylvania's radon guide gives a similar time scale for a related case: after windows that were letting in outdoor air are closed, radon "most often" returns to its old level within about 12 hours. Neither source measured a power outage as such.
Can I run a radon fan on a generator?
Yes, if the fan plugs in or an electrician has wired it to a circuit the generator feeds. The load is small: even a 310 W Festa Eagle is a minor part of a household generator's output. A fan that runs all day uses its watts times 24 hours, from about 0.4 kWh a day for an RP140 to about 7.4 kWh for an Eagle.
Will my radon alarm go off in a power outage?
It depends on the alarm. Festa's catalog lists a battery-powered digital gauge whose alarm "can be delayed for up to 99 hours in the settings menu to delay alarms during power outages." A plain U-tube manometer has no alarm; it just shows the vacuum dropping to zero. After the power comes back, look at your gauge to confirm the fan is pulling again.
How much does it cost to run a radon fan?
Minnesota's health department gives a quick rule: the fan's rated watts roughly equal its yearly cost in dollars at about $0.10 per kWh. A 66 W fan costs about $66 a year. Multiply by your own rate for a closer figure. Fantech puts the range for its own radon fans at ten dollars to several hundred dollars a year.
Sources and further reading
- RadonAway: RP Series Radon Mitigation Fan catalog sheet, P/N 02008 (RP140 to RP380 watts and CFM)
- RadonAway: GP Series Radon Mitigation Fan catalog sheet, P/N 02002 (GP201 to GP501 watts; hard wire or plug in)
- Festa Radon Technologies: 2022 product catalog (AMG Maverick 66 W, AMG Eagle 310 W, battery alarm with outage delay)
- Minnesota Department of Health: Calculating Energy Costs for Mitigation Systems (rated wattage of common radon fans)
- Fantech: Radon mitigation FAQ (fan off, operating cost)
- US EPA: How do I know if my radon mitigation system is working properly?
- Pennsylvania DEP: Pennsylvania Consumer's Guide to Radon Reduction
- South Carolina Radon Program: Living in a Home With a Radon Reduction System (March 2021)
- Ohio Department of Health: Radon booklet, Bureau of Environmental Health and Radiation Protection
- APC by Schneider Electric FAQ000210003: Back-UPS No-load Shutdown