Can a UPS Run a Gas Fireplace Blower in a Power Outage?

Yes. A UPS can run the blower on a gas fireplace or insert, and the fire itself usually needs no UPS at all: standing pilot models light with no power, and IntelliFire models light on 2 D or 4 AA batteries. A 1500 VA UPS runs a 35 to 184 W blower for roughly 4 hours down to about 40 minutes, but only if the blower has a cord you can reach.

On this page
  1. Which gas fireplaces light with no power
  2. Does the blower matter?
  3. What a fireplace blower draws
  4. Worked example: a corded blower on a 1500 VA UPS
  5. Runtime by blower rating
  6. Corded blower or hardwired junction box
  7. The speed control on a simulated sine UPS
  8. Power vent fireplaces
  9. What this answer does not cover
  10. Frequently asked questions

Yes, a UPS can run a gas fireplace blower in a power outage. A common 1500 VA unit runs one for about 40 minutes to 4 hours. The fire itself usually does not need the UPS. Most gas fireplaces light on their own in an outage, from a standing pilot or a small battery pack. What stops is the blower. A UPS can bring it back if the blower has a cord you can reach.

First, the terms. A blower (also called a fan kit) is the small electric fan under the firebox. It pushes room air around the hot firebox and back out through the grille. A standing pilot is a small flame that stays lit all the time and needs no outside power. An intermittent pilot (IPI) lights a fresh pilot with an electric spark each time you turn the fireplace on. IntelliFire is the IPI system used by Heat & Glo, Heatilator and Majestic. A power vent is an electric fan in the vent that pushes the exhaust outside. A UPS (uninterruptible power supply) is a battery box that keeps its outlets live when the wall power fails.

Which gas fireplaces light with no power

The makers settle this part. Heat & Glo and Heatilator both say a standing pilot fireplace "will light during a power outage." The reason: it "doesn't require electricity to activate the pilot flame." An intermittent pilot is different. It "requires electricity to spark the pilot flame each time the fireplace is used." That would leave you cold, but IntelliFire models carry a battery backup to light the pilot. IntelliFire takes two D cells. IntelliFire Plus takes four AA, and Majestic says IntelliFire Touch does too.

What lights in an outage, by ignition type (maker statements)
IgnitionLights with no power?Backup batterySource
Standing pilotYesNone neededHeat & Glo, Heatilator, Majestic
IntelliFire (IPI)Yes, on batteries2 D cellsHeat & Glo, Heatilator, Majestic
IntelliFire Plus (IPI+)Yes, on batteries4 AAHeat & Glo, Heatilator, Majestic
IntelliFire TouchYes, on batteries4 AAMajestic
Any IntelliFire model with a power ventNo"Not available"Hearth & Home IFT-RC400 guide

To run on batteries, find the control box and "slide this to ON for the appliance to operate with the power off" (Heat & Glo). Majestic adds that a model normally run from a remote or wall switch should be set to ON, rather than OFF or REMOTE. All three makers say to use the batteries only during an outage. Heat & Glo says the heat of the fireplace can shorten battery life.

Heatilator says the batteries are there for "lighting the pilot." Neither page says they run the blower. So the common case in an outage is a fireplace that lights and makes heat while the fan stays silent.

Does the blower matter?

For comfort, yes. For safety, no. DESA's GA3650TB instructions say "It is safe to operate fireplace with blower turned off." They add that the blower "helps distribute heated air." Napoleon says "Use of the fan increases the output of heat." That is the big difference from a pellet stove. There, the combustion blower clears the smoke, and losing it is a safety problem. On a gas fireplace without a power vent, the blower just spreads heat.

Blowers also turn on by themselves. A heat switch (a thermodisc) closes once the firebox warms. Napoleon says its blower starts 15 to 30 minutes after you light the fire. It keeps running 30 to 45 minutes after you turn the fire off. The sheet for an aftermarket GFK-160A kit puts the switch at about 120°F (49°C) on and 90°F (32°C) off. So the UPS sees no load for the first 15 minutes or more. It also keeps the blower going after the flame is off.

What a fireplace blower draws

Blower manuals rarely give watts. Some give amps. The watt figures people quote come from parts sellers. The table keeps the two apart.

Published electrical ratings for gas fireplace and insert blowers (115 to 120 V)
BlowerFitsRatingSource type
DESA GA3650TBDESA 32 in. fireplace systems (LFP33, VSGF33 and others)0.90 A at 120 V (108 VA)Maker instructions
Superior FAB-1100Superior fireplaces; also CGI-BAY and GI-3821 gas inserts1 A at 120 V (120 VA)Maker manual
Mendota D30 insert blowerMendota D30 gas insert"a 2 Amp power source is required"Maker manual (supply, not draw)
Napoleon GZ550-1KTNapoleon BGD33, BGD36, GD series and others35 W, 0.3 A at 115 VParts seller listing
Hearth & Home GFK-160AHeat & Glo, Heatilator, Quadra-Fire184 W, 1.60 A at 115 VParts seller listing
Regency 001-917Regency FP90 and EX90 wood fireplaces180 W, 2.0 A at 115 VParts seller listing

The maker manuals for the GFK-160A and GZ550-1KT give no watts or amps at all. The GFK-160A manual says only that it "operates on 120 VAC, 60 Hz power."

Our analysis: the seller "watts" are mostly volts times amps

Multiply the listings out. 115 V x 1.60 A is exactly 184, the GFK-160A's listed watts. 115 V x 0.3 A is 34.5, which rounds to the GZ550's 35 W. Those are VA figures, a ceiling, not a measured draw (see VA vs watts). The Regency listing does not even agree with itself: 115 V x 2.0 A is 230 VA, not 180 W. Use these numbers to size a UPS. For runtime, measure the real blower. A plug-in watt meter does it in a minute on a corded blower, at the speed you actually use; how to measure power draw covers the method.

Worked example: a corded blower on a 1500 VA UPS

Take a DESA 32 in. fireplace with the GA3650TB blower. The blower has a three-prong plug. It goes into "a properly grounded three-prong wall receptacle near" the fireplace. That makes it the easy case. Suppose the fireplace has a standing pilot. The blower is plugged into a 1500 VA UPS with two 12 V 9 Ah batteries (216 Wh).

The rating is 0.90 A at 120 V, so the blower draws 108 VA at most. Treat it as 108 W to be safe. The method is the one in why UPS runtime is not linear. It uses 85% inverter efficiency and a Peukert exponent of 1.15.

Battery load = 108 W / 0.85 = 127 W, or 5.3 A at 24 V
Runtime = 20 h x (9 Ah / (5.3 A x 20 h))^1.15 = about 1.17 h, or 70 minutes

Seventy minutes is a floor. The real draw is likely under 108 W, and lower still on a slower speed. Add the 15 minutes or more before the heat switch turns the blower on. On a smaller 750 VA UPS with one 12 V 9 Ah battery, the same blower gets about 32 minutes.

Runtime by blower rating

Here is the same math for each rating in the table above. These are new-battery figures. They assume the blower runs nonstop, which it does while the fire is lit.

Blower runtime on two common UPS sizes (85% efficiency, Peukert 1.15)
Blower load1500 VA, 2 x 12 V 9 Ah750 VA, 1 x 12 V 9 Ah
35 W (GZ550-1KT listing)about 4 h 15 minabout 1 h 55 min
108 W ceiling (DESA GA3650TB, 0.90 A)at least 70 minat least 32 min
120 W ceiling (Superior FAB-1100, 1 A)at least 62 minat least 28 min
184 W (GFK-160A listing)about 38 minabout 17 min

For your own blower, put the measured watts into the runtime calculator. For a whole evening, a UPS that takes extended battery packs, or a portable power station, holds far more energy. At 184 W, five hours is about 1,000 Wh before losses.

Corded blower or hardwired junction box

This is where most plans stop. A UPS has outlets, so it needs a plug to feed. Fireplace blowers get their power in three ways.

  • Cord to a wall outlet. The DESA GA3650TB plugs into a wall receptacle. The Mendota D30 manual offers the same option. It says to run the blower's 8-foot cord out of the insert cavity "to a wall electrical outlet in the room." Put the UPS between the plug and the wall. Done.
  • Plug inside the fireplace. Napoleon's GZ550-1KT has a cord. But it plugs into a receptacle in a junction box inside the fireplace. The GFK-160A gets its power "through a receptacle in the factory installed junction box." The plug is there, but the outlet is wired to the house.
  • Hardwired to the house. Heat & Glo's 6000TV manual says fan and remote kits need 110-120 VAC wired to the junction box. That happens "before the fireplace is permanently installed," and by "a licensed electrician." Napoleon wants its junction box connected and grounded "in accordance with local codes."

The second and third cases end the same way. You cannot plug a UPS into a junction box behind a fireplace front. Getting UPS power there means changing house wiring. An electrician can fit a power inlet and a transfer switch on that circuit. Or they can move the blower to a receptacle a UPS can feed. Hardwired vs plug-in UPS explains both. Mendota also says the supply "must be hot at all times" with no switch in it, so leave the UPS on.

Never backfeed

Do not push UPS power into a wall outlet with a male-to-male cord to reach the fireplace circuit. It powers wiring that should be dead and can hurt a line worker. Keep house power away from the valve, too. The GFK-160A manual warns "DO NOT CONNECT 110-120 VAC WIRING TO THE GAS CONTROL VALVE," and the 6000TV manual says that if you do, "THE VALVE WILL BE DESTROYED."

The speed control on a simulated sine UPS

Most fireplace blowers come with a dial to set the speed. The GFK-160A kit's listing calls its dial a "rheostat variable speed controller." Napoleon includes a "variable speed switch." Many lower-cost UPS units make a simulated sine wave on battery. That is a stepped output. It only roughly copies the smooth wave from the wall.

Speed dials and that stepped wave do not get along. Windy Nation's inverter guide lists "ceiling fan / motor speed control" among devices that "may not work properly." Its words: "speed control may not function." The reason it gives is that in a modified sine wave "the voltage rises and falls abruptly." A control that senses the shape of the wave then "will not work properly." None of the blower makers cited here mentions UPS waveform at all. Our advice is a pure sine wave UPS for any blower with a speed dial. That goes double if the UPS feeds the whole fireplace, control module and all, through an inlet.

Power vent fireplaces

A power vent model is the one gas fireplace here that does not light in an outage. Hearth & Home's IntelliFire Touch remote guide says it twice. "Cold-climate function and battery backup are disabled if a Power Vent is used." And: "Battery backup is not available if a Power Vent is installed." The guide also shows how much the vent fan does. It runs a 120 second pre-purge (a fan-only clearing run) before the flame lights. "The Power Vent is always ON when the flame is ON." After the flame is off, a post-purge of about 20 minutes follows.

So on a power vent fireplace, a blower-only UPS changes nothing. The fire needs 120 V from the house, and that circuit is hardwired. The only route is UPS or generator power to the whole circuit, through an inlet and transfer switch. That is electrician work. None of the sources here gives watts for a fireplace power vent. A clamp meter on the circuit during a full cycle tells you what to size for, as the gas furnace guide describes. The same pattern stops a power vent water heater.

Bottom line

Check the ignition first. A standing pilot or IntelliFire model will heat in an outage with no UPS, once you slide the switch to ON. Back up the blower only if its cord reaches a wall outlet. Expect about 70 minutes from a 108 W blower on a 1500 VA UPS. If the blower plugs in inside a junction box, or the fireplace has a power vent, call an electrician.

What this answer does not cover

The figures here come from a handful of blower kits and maker guides. Your fireplace may use a different kit. Read its manual and measure the blower before you buy a UPS. The ignition rules above are from Hearth & Home brands (Heat & Glo, Heatilator, Majestic). Other makers use other controls, and their battery backup, if any, works by their own manual. Vent-free gas logs and wood inserts follow other rules. The outdoor wood boiler guide covers a wood appliance where losing power is a real risk. Nothing here changes the makers' own safety rules for an outage. Keep anything that burns away from the fireplace, and keep children and pets back. Heat & Glo and Majestic both say not to use a fireplace that has been in water until a dealer checks it.

Practice once before winter

With the power on, slide the control box switch to ON with fresh batteries in place, and confirm the fireplace lights. If the blower has a cord on a UPS, light the fire, wait for the blower, then switch off the breaker feeding the UPS. Note how long the blower runs. Take the batteries out again when you are done.

Frequently asked questions

Is it safe to run a gas fireplace without the blower?

The blower spreads heat; it is not what keeps the fire safe. DESA's GA3650TB instructions say "It is safe to operate fireplace with blower turned off", and that the blower "helps distribute heated air." Expect less heat in the room, not a problem with the burner. Power vent models are the exception, since their vent fan is part of the venting.

How long do the IntelliFire backup batteries last?

None of the maker pages cited here gives a runtime. What they do say is how to use them: Majestic says batteries "are only to be used in the event of a power outage, not as your pilot's standard power source", and Heat & Glo says heat from the appliance can shorten battery life. Keep fresh spares, and take them out once power returns.

Will a UPS make my fireplace remote work in an outage?

It depends on the system. Heat & Glo's older 6000TV manual says its fan and remote kits need 110 to 120 VAC wired to the junction box, so a blower-only UPS does not help them. The IntelliFire Touch guide, by contrast, says to check the fireplace's backup batteries if the remote stops talking to it in an outage. Majestic's general advice is to set the control box switch to ON, not OFF or REMOTE.

Can I use a portable power station instead of a UPS?

Yes, for a corded blower. The blower turns on by itself once the firebox warms, so a short gap in power at switchover only delays it. Pick a station with pure sine output, so a speed control still works. A 35 W blower is a small load for any station; a 184 W blower uses about 1,000 Wh in five hours.

Does this apply to a wood stove insert blower?

The runtime math does. Regency's 001-917 kit for its FP90 and EX90 wood fireplaces is listed at 180 W and 2.0 A. In a 2019 hearth.com thread about a wood insert, a moderator wrote that it "will be ok running without the blower. It won't put out as much heat." Check your own manual first.

Sources and further reading

  1. Heat & Glo: Using Your Fireplace or Stove During a Power Outage
  2. Heatilator: Using Your Fireplace or Insert During a Power Outage
  3. Heatilator: Battery Backup Systems for Gas Fireplaces
  4. Majestic: Operating Your Fireplace During a Power Outage
  5. Hearth & Home Technologies: IFT-RC400 IntelliFire Touch Remote Control User Guide (2326-983 Rev. L)
  6. Heat & Glo: 6000TV-OAK Owner's Manual (384-900 Rev. N)
  7. Hearth & Home Technologies: GFK-160A Blower System Installation and Operating Instructions
  8. Napoleon (Wolf Steel): GZ550-1KT Blower Installation Instructions (W415-0135)
  9. DESA: GA3650TB Blower Accessory Installation Instructions (108321-01B)
  10. Lennox Hearth Products: Superior FAB-1100 Blower Manual (903249 Rev. E)
  11. Mendota: D30 Installation and Operating Instructions, blower power
  12. Pellet Stove Parts 4 Less: Napoleon GZ550-1KT listing (35 W, 0.3 A)
  13. Fireplace Blowers Online: GFK-160A kit listing (184 W, 1.60 A)
  14. Fireplace Blowers Online: GFK-160A aftermarket fan kit installation instructions
  15. Fireplace Blowers Online: Regency 001-917 kit listing (180 W, 2.0 A)
  16. Windy Nation: Advantages of Pure Sine Wave Inverters over Modified Sine Wave Inverters
  17. hearth.com forum: Power insert blower during power outage? (January 2019)